Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 1000783 DEA: 041Q7004 EFIS: 0418000319
QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-101-22.8/32.8
Work Description: REPLACE BRIDGE RAILING AND GUARDRAIL, & RECONSTRUCT SIDEWALK.
Location Description: SONOMA COUNTY AT VARIOUS LOCATIONS FROM MENDOCINO AVENUE OVERCROSSING TO LIMERICK LANE OVERCROSSING
Contractor Name: GHILOTTI CONSTRUCTION COMPANY, INC.
Contractor Address: Unknown
Resident Engineer: Leonard Brajnikoff Structure Rep.: Nick Abuhamdieh
DIME Sample ID: 2025-08-18-47
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Santa Rosa
Sample Organization Contact: (510) 774-6009
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/18/2025
Date that the sample was received by the laboratory/organization performing the testing: 08/18/2025
The quantity of what the sample constitutes: 10
A brief description of the sample: 675 BDSA
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Superior Supplies Ready Mix
The concrete mix design number: 675BDSA
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 311685
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: WHEEL BARROW
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2025-08-18-47-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/16/2025
Date Tested: 09/15/2025
Submitted By Organization: Kleinfelder - Hayward
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5090 psi
|
|
Maximum load on cylinder 1
|
66672 lb
|
|
Maximum load on cylinder 2
|
64495 lb
|
|
Maximum load on cylinder 3
|
61179 lb
|
|
Compressive strength of cylinder 1
|
5278.9 psi
|
|
Type of fracture pattern of cylinder 1
|
6
|
|
Compressive strength of cylinder 2
|
5130.9 psi
|
|
Compressive strength of cylinder 3
|
4867.1 psi
|
|
Type of fracture pattern of cylinder 2
|
5
|
|
Type of fracture pattern of cylinder 3
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data
|
DIME Test ID: 2025-08-18-47-2
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Submitted By Organization: CT SC - 3672 - Santa Rosa
Organization Address: 4030 Occidental, Building B,
Organization City: Santa Rosa
Organization State: CA
Organization Zipcode: 95401
Organization Email: james.cook@dot.ca.gov
Organization Phone: (707) 974-2571
Data has not been verified.
DIME Test ID: 2025-08-18-47-3
Test Method: ASTM C143-15a: Standard Test Method for Slump of Hydraulic-Cement Concrete
Submitted By Organization: CT SC - 3672 - Santa Rosa
Organization Address: 4030 Occidental, Building B,
Organization City: Santa Rosa
Organization State: CA
Organization Zipcode: 95401
Organization Email: james.cook@dot.ca.gov
Organization Phone: (707) 974-2571
Data has not been verified.
DIME Test ID: 2025-08-18-47-4
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Submitted By Organization: CT SC - 3672 - Santa Rosa
Organization Address: 4030 Occidental, Building B,
Organization City: Santa Rosa
Organization State: CA
Organization Zipcode: 95401
Organization Email: james.cook@dot.ca.gov
Organization Phone: (707) 974-2571
Data has not been verified.