Sample Record for 2025-08-08-19
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 1000665 DEA: 081K4004 EFIS: 0819000031
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-3.5/6.8
Work Description: HMA (TYPE A), RDWY EXC, STR CONC RET WALL, RUBBERIZED HMA (OGFC).
Location Description: TEMECULA FROM 0.1 MI NORTH OF TEMECULA PARKWAY TO 0.2 MI NORTH OF WINCHESTER ROAD
Contractor Name: BEADOR CONSTRUCTION COMPANY, INC.
Contractor Address: 2900 Bristol Street, Suite D204, Costa Mesa, CA 92626
Resident Engineer: Denise Sostrom Structure Rep.: Gizachew Abayneh
Sample Information
DIME Sample ID: 2025-08-08-19
TL Number from the TL Form: 1079-08
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/08/2025
Date that the sample was received by the laboratory/organization performing the testing: 08/11/2025
The quantity of what the sample constitutes: 9
A brief description of the sample: concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1079-08
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: na
Material Information
The concrete mix design number: 1610974
The truck number from where the sample was collected: 10070462
The batch plant ticket number from where the sample was collected: 41300263
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Rte15 SB STA22+00-19+75, Bottom of Footing Ret. Wall
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 3
DIME Test ID: 2025-08-08-19-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap Cured in accordance with ASTM C511
Verified Date: 08/15/2025
Date Tested: 08/15/2025
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Compressive strength (to nearest 10 psi)
|
4880 psi
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Compressive strength of cylinder 1
|
4623.7 psi
|
|
Compressive strength of cylinder 2
|
4966.0 psi
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Compressive strength of cylinder 3
|
5043.5 psi
|
|
Maximum load on cylinder 1
|
58120 lb
|
|
Maximum load on cylinder 2
|
62720 lb
|
|
Maximum load on cylinder 3
|
63700 lb
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
Test 2 of 3
DIME Test ID: 2025-08-08-19-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap Cured in accordance with ASTM C511
Verified Date: 08/29/2025
Date Tested: 08/22/2025
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Compressive strength (to nearest 10 psi)
|
5590 psi
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Compressive strength of cylinder 1
|
5733.2 psi
|
|
Compressive strength of cylinder 2
|
5424.0 psi
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Compressive strength of cylinder 3
|
5621.3 psi
|
|
Maximum load on cylinder 1
|
72410 lb
|
|
Maximum load on cylinder 2
|
68180 lb
|
|
Maximum load on cylinder 3
|
70660 lb
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
14 days
|
Test 3 of 3
DIME Test ID: 2025-08-08-19-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap Cured in accordance with ASTM C511
Verified Date: 09/18/2025
Date Tested: 09/05/2025
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Compressive strength (to nearest 10 psi)
|
5890 psi
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Compressive strength of cylinder 1
|
5965.8 psi
|
|
Compressive strength of cylinder 2
|
5884.4 psi
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Compressive strength of cylinder 3
|
5833.7 psi
|
|
Maximum load on cylinder 1
|
74990 lb
|
|
Maximum load on cylinder 2
|
74320 lb
|
|
Maximum load on cylinder 3
|
73330 lb
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|