Sample Record for 2025-08-11-15
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 215620 DEA: 01436404 EFIS: 0100000193
QA Service Level: 1
DIST-CO-RTE-PM: 01-DN-101-35.8/36.5
Work Description: Dr. Fine Bridge Replacement
Location Description: DR. FINE BRIDGE REPLACEMENT FROM LAKE EARL DR TO S FRED D. HAIGHT DR ON HWY 101 ACROSS SMITH RIVER.
Contractor Name: MCM Construction
Contractor Address: PO Box 620, North Highlands, Ca 95660
Resident Engineer: Clayton Malmberg Structure Rep.: Brian Cinkutis
Sample Information
DIME Sample ID: 2025-08-11-15
TL Number from the TL Form:
Sample Submitted By Organization: CT D01 - Crescent City Field Laboratory
Sample Organization Contact: (707) 496-5581
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/11/2025
Date that the sample was received by the laboratory/organization performing the testing: 08/12/2025
The quantity of what the sample constitutes: 260 CY
A brief description of the sample: Span 4 stem and soffit
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Tidewater Starry pit
Material Information
The concrete mix design number: SR-minor structure NA
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: xxxx
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: back of truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 4
DIME Test ID: 2025-08-11-15-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 08/26/2025
Date Tested: 08/26/2025
Submitted By Organization: CT D01 - Crescent City Field Laboratory
Organization Address: 1444 Parkway Dr.,
Organization City: Crescent City
Organization State: CA
Organization Zipcode: 95531
Organization Email: clayton.malmberg@dot.ca.gov
Organization Phone: (707) 496-5581
General Comments for this Test: 14* day break
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4560 psi
|
|
Maximum load on cylinder 1
|
57418 lb
|
|
Maximum load on cylinder 2
|
56873 lb
|
|
Maximum load on cylinder 3
|
57782 lb
|
|
Compressive strength of cylinder 1
|
4567.9 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
4524.5 psi
|
|
Compressive strength of cylinder 3
|
4596.8 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
15 days
|
|
Age of specimen in hours
|
no data0 hours
|
Test 2 of 4
DIME Test ID: 2025-08-11-15-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 09/08/2025
Date Tested: 09/08/2025
Submitted By Organization: CT D01 - Crescent City Field Laboratory
Organization Address: 1444 Parkway Dr.,
Organization City: Crescent City
Organization State: CA
Organization Zipcode: 95531
Organization Email: clayton.malmberg@dot.ca.gov
Organization Phone: (707) 496-5581
General Comments for this Test: 28 day break
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5470 psi
|
|
Maximum load on cylinder 1
|
68365 lb
|
|
Maximum load on cylinder 2
|
70355 lb
|
|
Maximum load on cylinder 3
|
67496 lb
|
|
Compressive strength of cylinder 1
|
5438.7 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
5597.1 psi
|
|
Compressive strength of cylinder 3
|
5369.6 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|
Test 3 of 4
DIME Test ID: 2025-08-11-15-4
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Submitted By Organization: CT D01 - Crescent City Field Laboratory
Organization Address: 1444 Parkway Drive,RSP #492
Organization City: Crescent City
Organization State: CA
Organization Zipcode: 95531
Organization Email: clayton.malmberg@dot.ca.gov
Organization Phone: (707) 496-5581
This test has been superseded on 09/03/2025.
Reason: corrected
Test 4 of 4
DIME Test ID: 2025-08-11-15-5
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 09/03/2025
Date Tested: 08/18/2025
Submitted By Organization: CT D01 - Crescent City Field Laboratory
Organization Address: 1444 Parkway Dr.,
Organization City: Crescent City
Organization State: CA
Organization Zipcode: 95531
Organization Email: clayton.malmberg@dot.ca.gov
Organization Phone: (707) 496-5581
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3270 psi
|
|
Maximum load on cylinder 1
|
40280 lb
|
|
Maximum load on cylinder 2
|
41652 lb
|
|
Maximum load on cylinder 3
|
41431 lb
|
|
Compressive strength of cylinder 1
|
3204.5 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
3313.6 psi
|
|
Compressive strength of cylinder 3
|
3296 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|