Sample Record for 2024-06-19-162
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 994396 DEA: 07330304 EFIS: 0716000213
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-10-22.0/30.8
Work Description: CONSTRUCT CONCRETE BARRIER AND STRUCTURAL CONCRETE BARRIER SLAB.
Location Description: LOS ANGELES COUNTY AT VARIOUS LOCATIONS FROM 0.6 MILE EAST OF ROUTE 710/10 SEPARATION TO 0.3 MILE WEST OF ROUTE 10/605 SEPARATION
Contractor Name: FEC FUTURE CONTRACTORS AND ENGINEERS, INC.
Contractor Address: 184 TECHNOLOGY DRIVE, SUITE 2, IRVINE CA 92618
Resident Engineer: Edgar Herrera Structure Rep.: Ryan Ramos
Sample Information
DIME Sample ID: 2024-06-19-162
TL Number from the TL Form:
Sample Submitted By Organization: RMA Group - Rancho Cucamonga
Sample Organization Contact: (909) 989-1751
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 06/19/2024
Date that the sample was received by the laboratory/organization performing the testing: 06/19/2024
The quantity of what the sample constitutes: 6
A brief description of the sample: Structural Concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: Barrier
The fabricator/manufacturer/facility name: Robertson's Ready Mix
Material Information
The concrete mix design number: SC590B33
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 821604
Concrete batch plant: Irwindale Plant
The fabricator/manufacturer designation for the sample: Robertson's Ready Mix
A detailed description of where the material sample was collected: Rte10 EB Durfee Exit, Center Median Concrete Barrier
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 2
DIME Test ID: 2024-06-19-162-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 07/29/2025
Date Tested: 06/26/2024
Submitted By Organization: RMA Group - Rancho Cucamonga
Organization Address: 12130 Santa Margarita Court,
Organization City: Rancho Cucamonga
Organization State: CA
Organization Zipcode: 91730
Organization Email: cbachler@rmacompanies.com
Organization Phone: (909) 989-1751
General Comments for this Test: Average compressive strength - 3020psi.
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With density determined by dimension measurements
|
|
Average cylinder density (to nearest 1 pcf)
|
148 lb/ft^3
|
|
Average diameter of cylinder 1
|
6.00 in
|
|
Average diameter of cylinder 2
|
6.00 in
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Test 2 of 2
DIME Test ID: 2024-06-19-162-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 07/29/2025
Date Tested: 07/17/2024
Submitted By Organization: RMA Group - Rancho Cucamonga
Organization Address: 12130 Santa Margarita Court,
Organization City: Rancho Cucamonga
Organization State: CA
Organization Zipcode: 91730
Organization Email: cbachler@rmacompanies.com
Organization Phone: (909) 989-1751
General Comments for this Test: Average compressive strength - 4520psi.
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With density determined by dimension measurements
|
|
Average cylinder density (to nearest 1 pcf)
|
148 lb/ft^3
|
|
Average diameter of cylinder 1
|
6.00 in
|
|
Average diameter of cylinder 2
|
6.00 in
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|