Print Report | Back to Sample Detail

Sample Record for 2025-07-20-9

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994864 DEA: 050N74U4 EFIS: 0522000025 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-9.9/10.6
Work Description: SB 101 4D North San Ysidro to Olive Mill
Location Description: In Santa Barbara County in and near Santa Barbara from 0.1 mile south of San Ysidro Road Overcrossing to 0.1 north of Olive Mill Road Overcrossing
Contractor Name: Craig Flowers (Granite Construction Company)
Contractor Address: PO Box 6744, Santa Barbara, CA 93160
Resident Engineer: Taylor Merlo Structure Rep.: Emiliano Berntsen

Sample Information

DIME Sample ID: 2025-07-20-9
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 07/20/2025
Date that the sample was received by the laboratory/organization performing the testing: 07/23/2025
The quantity of what the sample constitutes: 288
A brief description of the sample: Dayton Superior coupler
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CMC Rebar Dayton Superior

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: CMC
Coupler Manufacturer: Dayton Superior
Intermediate Assembler or Fabricator:
Rebar Size: #8
Coupler Model: D250L Bar Lock
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): 4000005510 / 202937
Rebar Heat Number(s): 9008229
Rebar Size 2 : 8
Coupler Unique ID: SL-17-06

Test Results

Test 1 of 1

DIME Test ID: 2025-07-20-9-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 07/31/2025
Date Tested: 07/31/2025
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 4
SampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
1180.790.00579250100000service spliceKleinfelder
2180.79000082210104000service spliceKleinfelder
3180.79000081110103000service spliceKleinfelder
4180.79000081060103000service spliceKleinfelder
Temperature 0 f
UTM NA
Halo ID na