Project ID: 994978 DEA: 09379504 EFIS: 0919000009
QA Service Level: 1
DIST-CO-RTE-PM: 09-INY-5709-
Work Description: CONSTRUCT BUILDING AND PLACE HMA.
Location Description: INYO COUNTY AT INDEPENDENCE AT THE INDEPENDENCE MAINTENANCE STATION AT 665 NORTH EDWARDS STREET
Contractor Name: FEC FUTURE CONTRACTORS AND ENGINEERS INC
Contractor Address: 184 Technology Drive, Irvine, CA 92618
Resident Engineer: George Elzawy Structure Rep.: Derek Armon
DIME Sample ID: 2025-07-08-5
TL Number from the TL Form: 4702
Sample Submitted By Organization: CT D09 - Bishop Field Laboratory
Sample Organization Contact: (760) 872-5211
Type of Sample: Production Start-Up
Type of Material: Hot Mix Asphalt
Sample Taken Date: 07/08/2025
Date that the sample was received by the laboratory/organization performing the testing: 07/08/2025
The quantity of what the sample constitutes: 500 Tons
A brief description of the sample: 3/4" HMA-A-SP PG58-34M R18
From where was the sample collected: Source
Laboratory sample identification: PSU-1
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: RHB Plant Independence
DIME Test ID: 2025-07-08-5-1
Test Method: AASHTO T209-22: Standard Method of Test for Theoretical Maximum Specific Gravity (Gmm) and Density of Asphalt Mixtures (Maximum Specific Gravity)
Verified Date: 07/09/2025
Date Tested: 07/08/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PSU-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Number of Samples
|
1
|
|
What is the unit of measurement for theoretical density?
|
US Units
|
|
Mass Determination
|
Air
|
|
Method Performed
|
Mechanical Agitation - Method A
|
|
Mass of container filled with water 1
|
7310.5 grams
|
|
Mass of oven-dry sample in air for Sample 1
|
2189.2 grams
|
|
Mass of container filled with the sample and water for Sample 1
|
8621.6 grams
|
|
Temperature of Water
|
77.2 °F
|
|
Specific Gravity for Sample 1
|
2.493
|
|
Theoretical maximum density at 25°C (77°F)
|
155.2 lb/ft^3
|
DIME Test ID: 2025-07-08-5-2
Test Method: AASHTO T308-10: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 07/09/2025
Date Tested: 07/08/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PSU-1
Test Result Compliance: complies
Additional Comments When Verified:
|
What temperature unit is used?
|
Celsius
|
|
Test procedure used?
|
Method A
|
|
Mass of the specimen basket assembly
|
4247.4 g
|
|
Mass of the specimen and specimen basket assembly prior to ignition
|
6530 g
|
|
Mass of HMA Sample prior to ignition
|
2282.6 g
|
|
Corrected Asphalt Binder Content
|
4.94 %
|
|
Mass Loss
|
122 g
|
|
Mass of aggregate remaining after ignition
|
2160.6 g
|
|
Correction Factor (Percent by mass of HMA Specimen)
|
0.4 %
|
|
Moisture Content
|
no data0 %
|
|
Temperature Compensation Factor
|
no data0 %
|
|
Test Temperature
|
538 C
|
DIME Test ID: 2025-07-08-5-3
Test Method: AASHTO T30-19: Standard Method of Test for Mechanical Analysis of Extracted Aggregate (Mechanical Analysis)
Verified Date: 07/09/2025
Date Tested: 07/08/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PSU-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Is an aggregate correction factor used?
|
No
|
|
Cumulative percent passing the 2 in. sieve
|
100 %
|
|
Cumulative percent passing the 1 1/2 in. sieve
|
100 %
|
|
Cumulative percent passing the 1 in. sieve
|
100 %
|
|
Cumulative percent passing the 3/4 in. sieve
|
98 %
|
|
Cumulative percent passing the 1/2 in. sieve
|
90 %
|
|
Cumulative percent passing the 3/8 in. sieve
|
82 %
|
|
Cumulative percent passing the #4 sieve
|
52 %
|
|
Cumulative percent passing the #8 sieve
|
37 %
|
|
Cumulative percent passing the #16 sieve
|
26 %
|
|
Cumulative percent passing the #30 sieve
|
18 %
|
|
Cumulative percent passing the #50 sieve
|
11 %
|
|
Cumulative percent passing the #100 sieve
|
7 %
|
|
Cumulative percent passing the #200 sieve
|
4.1 %
|
DIME Test ID: 2025-07-08-5-4
Test Method: AASHTO T275-07r12: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Paraffin-Coated Specimens (Bulk Specific Gravity)
Verified Date: 07/09/2025
Date Tested: 07/08/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PSU-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Bulk Specific Gravity
|
2.375
|
|
Bulk Specific Gravity 2
|
2.381
|
|
Bulk Specific Gravity 3
|
2.38
|
|
Average Bulk Specific Gravity
|
2.379
|
DIME Test ID: 2025-07-08-5-5
Test Method: AASHTO T269-14: Standard Method of Test for Percent Air Voids in Compacted Dense and Open Asphalt Mixtures (Air Void)
Verified Date: 07/09/2025
Date Tested: 07/08/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PSU-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Percent Air Voids
|
4.7 %
|
|
Percent Air Voids 2
|
4.5 %
|
|
Percent Air Voids 3
|
4.5 %
|
|
Average Percent Air Voids
|
4.6 %
|
DIME Test ID: 2025-07-08-5-6
Test Method: AASHTO T166-16: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Saturated Surface-Dry Specimens (Method A)
Verified Date: 07/09/2025
Date Tested: 07/08/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PSU-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Number of tests
|
4
|
|
Bulk Specific Gravity 1
|
2.316
|
|
Bulk Specific Gravity 2
|
2.316
|
|
Bulk Specific Gravity 3
|
2.313
|
|
Bulk Specific Gravity 4
|
2.313
|
|
Percent of water absorbed by volume 1
|
0.58 %
|
|
Percent of water absorbed by volume 2
|
0.55 %
|
|
Percent of water absorbed by volume 3
|
0.62 %
|
|
Percent of water absorbed by volume 4
|
0.6 %
|
|
Average Bulk Specific Gravity
|
2.314
|
DIME Test ID: 2025-07-08-5-7
Test Method: AASHTO T324-14: Standard Method of Test for Hamburg Wheel-Track Testing of Compacted Asphalt Mixtures (Hamburg Wheel Track)
Verified Date: 07/09/2025
Date Tested: 07/08/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PSU-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Specified minimum number of passes at ½” rut depth, or number of passes at ½” rut depth if applicable (Wheel A)
|
15000
|
|
Specified minimum number of passes at ½” rut depth, or number of passes at ½” rut depth if applicable (Wheel B)
|
15000
|
|
Impression at specified number of passes, or specified maximum impression if applicable (Wheel A)
|
3.01 mm
|
|
Impression at specified number of passes, or specified maximum impression if applicable (Wheel B)
|
2.91 mm
|
|
Stripping Inflection Point (Wheel A)
|
0
|
|
Stripping Inflection Point (Wheel B)
|
0
|