Project ID: 993818 DEA: 07322504 EFIS: 0716000056
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-103-0.1/0.1
Work Description: UNION PACIFIC OH DECK REHABILITATION
Location Description: THE CITY AND COUNTY OF LOS ANGELES AT UNION PACIFIC OVERHEAD
Contractor Name: BEADOR CONSTRUCTION COMPANY, INC.
Contractor Address: 2900 Bristol Street, Suite D204, Costa Mesa, CA 92626
Resident Engineer: Thang Ton Structure Rep.: Sami Deeb
DIME Sample ID: 2025-05-22-75
TL Number from the TL Form: 9202024
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 05/22/2025
Date that the sample was received by the laboratory/organization performing the testing: 05/28/2025
The quantity of what the sample constitutes: 130 CY
A brief description of the sample: 4X8 PCC cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 25-196
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: National Ready Mix Concrete Company
The concrete mix design number: L85E540T1X
The truck number from where the sample was collected: 0906
The batch plant ticket number from where the sample was collected: 7385624
Concrete batch plant: National Ready Mix Concrete Company
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2025-05-22-75-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 06/30/2025
Date Tested: 06/19/2025
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.03 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.02 in
|
|
Cross sectional area of cylinder 1
|
12.76 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.69 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5200 psi
|
|
Maximum load on cylinder 1
|
68776 lb
|
|
Maximum load on cylinder 2
|
63156 lb
|
|
Maximum load on cylinder 3
|
66242 lb
|
|
Compressive strength of cylinder 1
|
5390.0 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
5000.5 psi
|
|
Compressive strength of cylinder 3
|
5220 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|