Sample Record for 2025-06-05-46

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994574 DEA: 050C7334 EFIS: 0518000116 QA Service Level: 1
DIST-CO-RTE-PM: 05-SCR-1-10.5/13.4
Work Description: CONSTRUCT OVERCROSSING AND AUXILIARY LANE/ Replace Capitola Ave OC + RWs and SWs
Location Description: SANTA CRUZ COUNTY IN AND NEAR CITY OF CAPITOLA FROM STATE PARK DRIVE OVERCROSSING TO 0.2 MILE NORTH OF BAY AVENUE UNDERCROSSING
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 580 West Beach Street, Watsonville, CA 95076
Resident Engineer: Fernando Dos Santos Structure Rep.: Daniel Dait

Sample Information

DIME Sample ID: 2025-06-05-46
TL Number from the TL Form:
Sample Submitted By Organization: Construction Testing Services
Sample Organization Contact: (925) 351-6905
Type of Sample: Quality Control
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 06/05/2025
Date that the sample was received by the laboratory/organization performing the testing: 06/06/2025
The quantity of what the sample constitutes: 8 HRC Coupler Assemblies
A brief description of the sample: HRC Couplers
From where was the sample collected: Fabricator
Laboratory sample identification: 291299
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Associated Rebar

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Ultimate
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: CMC/Nucor
Coupler Manufacturer: HRC
Intermediate Assembler or Fabricator:
Rebar Size: #5
Coupler Model: HRC 500/510
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): 79013707
Rebar Heat Number(s): 4148669, 3500042213
Rebar Size 2 :
Coupler Unique ID: TP-17-03

Test Results

Test 1 of 1

DIME Test ID: 2025-06-05-46-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 06/11/2025
Date Tested: 06/10/2025
Submitted By Organization: Construction Testing Services
Organization Address: 2118 Rheem Drive,
Organization City: Pleasanton
Organization State: CA
Organization Zipcode: 94588
Organization Email: rring@cts-1.com
Organization Phone: (925) 351-6905
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 8
SampleMfg. Lot Number(s)SizeArea (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
1150.312906093742PassJon Garland
2150.312894093355PassJon Garland
3150.312902093613PassJon Garland
4150.312902093613PassJon Garland
1450.312902093613PassJon Garland
2450.312884093032PassJon Garland
3450.312894093355PassJon Garland
4450.312888093161PassJon Garland
UTM NA
Temperature 68 f