Print Report | Back to Sample Detail

Sample Record for 2025-05-15-65

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994525 DEA: 031H9904 EFIS: 0317000043 QA Service Level: 1
DIST-CO-RTE-PM: 03-PLA,NEV-80-68.3/69.7,0.0/R2.7
Work Description: RDWY EXC, PLACE HMA & JPCP, SLAB REPLACEMENT & POLYESTER CONC OVERLAY.
Location Description: PLACER AND NEVADA COUNTIES NEAR KINGVALE FROM 0.3 MILE WEST OF TROY UNDERCROSSING TO 0.2 MILE EAST OF SODA SPRINGS OVERCROSSING
Contractor Name: A. TEICHERT & SON INC DBA TEICHERT CONSTRUCTION
Contractor Address: 4401 Duluth Avenue, Rocklin, CA 95765
Resident Engineer: Randie Babbini Structure Rep.: Carl Anderson

Sample Information

DIME Sample ID: 2025-05-15-65
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 05/15/2025
Date that the sample was received by the laboratory/organization performing the testing: 06/20/2025
The quantity of what the sample constitutes: 8
A brief description of the sample: #9 HRC Coupler
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: hrc

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Ultimate
Material Standard Code: ASTM A706
Material Grade: 80
Rebar Manufacturer: Nucor
Coupler Manufacturer: HRC
Intermediate Assembler or Fabricator:
Rebar Size: #9
Coupler Model: HRC 500M
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): Y5156
Rebar Heat Number(s): 1202067444
Rebar Size 2 :
Coupler Unique ID: TP-17-06

Test Results

Test 1 of 1

DIME Test ID: 2025-05-15-65-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 07/01/2025
Date Tested: 07/01/2025
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 4
SampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
11910.0051111020111020ok neckingAtlas
21910000111760111760ok neckingAtlas
31910000112460112460ok neckingAtlas
41910000111190111190ok neckingAtlas
Temperature 0 f
UTM NA
Halo ID na