Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 994978 DEA: 09379504 EFIS: 0919000009
QA Service Level: 1
DIST-CO-RTE-PM: 09-INY-5709-
Work Description: CONSTRUCT BUILDING AND PLACE HMA.
Location Description: INYO COUNTY AT INDEPENDENCE AT THE INDEPENDENCE MAINTENANCE STATION AT 665 NORTH EDWARDS STREET
Contractor Name: FEC FUTURE CONTRACTORS AND ENGINEERS INC
Contractor Address: 184 Technology Drive, Irvine, CA 92618
Resident Engineer: George Elzawy Structure Rep.: Derek Armon
DIME Sample ID: 2025-06-03-25
TL Number from the TL Form: JMF-01
Sample Submitted By Organization: CT D09 - Bishop Field Laboratory
Sample Organization Contact: (760) 872-5211
Type of Sample: Verification
Type of Material: Hot Mix Asphalt
Sample Taken Date: 06/03/2025
Date that the sample was received by the laboratory/organization performing the testing: 06/03/2025
The quantity of what the sample constitutes: JMF Verification
A brief description of the sample: 3/4" HMA-A-SP PG64-28M R15
From where was the sample collected: Source
Laboratory sample identification: 4611
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Granite 5 Bridges Plant Bishop
DIME Test ID: 2025-06-03-25-1
Test Method: AASHTO T209-22: Standard Method of Test for Theoretical Maximum Specific Gravity (Gmm) and Density of Asphalt Mixtures (Maximum Specific Gravity)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Number of Samples
|
1
|
|
What is the unit of measurement for theoretical density?
|
US Units
|
|
Mass Determination
|
Air
|
|
Method Performed
|
Mechanical Agitation - Method A
|
|
Mass of container filled with water 1
|
7310.5 grams
|
|
Mass of oven-dry sample in air for Sample 1
|
2091 grams
|
|
Mass of container filled with the sample and water for Sample 1
|
8554.5 grams
|
|
Temperature of Water
|
77.2 °F
|
|
Specific Gravity for Sample 1
|
2.469
|
|
Theoretical maximum density at 25°C (77°F)
|
153.7 lb/ft^3
|
DIME Test ID: 2025-06-03-25-2
Test Method: AASHTO T308-10: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
|
What temperature unit is used?
|
Celsius
|
|
Test procedure used?
|
Method A
|
|
Mass of the specimen basket assembly
|
4274 g
|
|
Mass of the specimen and specimen basket assembly prior to ignition
|
6362.6 g
|
|
Mass of HMA Sample prior to ignition
|
2088.6 g
|
|
Corrected Asphalt Binder Content
|
4.56 %
|
|
Mass Loss
|
107.4 g
|
|
Mass of aggregate remaining after ignition
|
1981.2 g
|
|
Correction Factor (Percent by mass of HMA Specimen)
|
0.58 %
|
|
Moisture Content
|
no data0 %
|
|
Temperature Compensation Factor
|
no data0 %
|
|
Test Temperature
|
538 C
|
DIME Test ID: 2025-06-03-25-3
Test Method: AASHTO T275-07r12: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Paraffin-Coated Specimens (Bulk Specific Gravity)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Bulk Specific Gravity
|
2.371
|
|
Bulk Specific Gravity 2
|
2.378
|
|
Bulk Specific Gravity 3
|
2.373
|
|
Average Bulk Specific Gravity
|
2.374
|
DIME Test ID: 2025-06-03-25-4
Test Method: AASHTO T269-14: Standard Method of Test for Percent Air Voids in Compacted Dense and Open Asphalt Mixtures (Air Void)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Percent Air Voids
|
4 %
|
|
Percent Air Voids 2
|
3.7 %
|
|
Percent Air Voids 3
|
3.9 %
|
|
Average Percent Air Voids
|
3.9 %
|
DIME Test ID: 2025-06-03-25-5
Test Method: AASHTO T166-16: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Saturated Surface-Dry Specimens (Method A)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
|
Number of tests
|
6
|
|
Bulk Specific Gravity 1
|
2.279
|
|
Bulk Specific Gravity 2
|
2.308
|
|
Bulk Specific Gravity 3
|
2.319
|
|
Bulk Specific Gravity 4
|
2.306
|
|
Bulk Specific Gravity 5
|
2.308
|
|
Bulk Specific Gravity 6
|
2.308
|
|
Percent of water absorbed by volume 1
|
0.47 %
|
|
Percent of water absorbed by volume 2
|
0.35 %
|
|
Percent of water absorbed by volume 3
|
0.43 %
|
|
Percent of water absorbed by volume 4
|
0.36 %
|
|
Percent of water absorbed by volume 5
|
0.42 %
|
|
Percent of water absorbed by volume 6
|
0.25 %
|
|
Average Bulk Specific Gravity
|
2.305
|
DIME Test ID: 2025-06-03-25-6
Test Method: AASHTO T324-14: Standard Method of Test for Hamburg Wheel-Track Testing of Compacted Asphalt Mixtures (Hamburg Wheel Track)
Verified Date: 06/05/2025
Date Tested: 06/05/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-01
Test Result Compliance: complies
Additional Comments When Verified:
|
Specified minimum number of passes at ½” rut depth, or number of passes at ½” rut depth if applicable (Wheel A)
|
15000
|
|
Specified minimum number of passes at ½” rut depth, or number of passes at ½” rut depth if applicable (Wheel B)
|
15000
|
|
Impression at specified number of passes, or specified maximum impression if applicable (Wheel A)
|
3.09 mm
|
|
Impression at specified number of passes, or specified maximum impression if applicable (Wheel B)
|
2.24 mm
|
|
Stripping Inflection Point (Wheel A)
|
0
|
|
Stripping Inflection Point (Wheel B)
|
0
|