Project Information

Project ID: 994978 DEA: 09379504 EFIS: 0919000009 QA Service Level: 1
DIST-CO-RTE-PM: 09-INY-5709-
Work Description: CONSTRUCT BUILDING AND PLACE HMA.
Location Description: INYO COUNTY AT INDEPENDENCE AT THE INDEPENDENCE MAINTENANCE STATION AT 665 NORTH EDWARDS STREET
Contractor Name: FEC FUTURE CONTRACTORS AND ENGINEERS INC
Contractor Address: 184 Technology Drive, Irvine, CA 92618
Resident Engineer: George Elzawy Structure Rep.: Derek Armon

Sample Information

DIME Sample ID: 2025-06-03-25
TL Number from the TL Form: JMF-01
Sample Submitted By Organization: CT D09 - Bishop Field Laboratory
Sample Organization Contact: (760) 872-5211
Type of Sample: Verification
Type of Material: Hot Mix Asphalt
Sample Taken Date: 06/03/2025
Date that the sample was received by the laboratory/organization performing the testing: 06/03/2025
The quantity of what the sample constitutes: JMF Verification
A brief description of the sample: 3/4" HMA-A-SP PG64-28M R15
From where was the sample collected: Source
Laboratory sample identification: 4611
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Granite 5 Bridges Plant Bishop

Material Information

HMA Type: Type A HMA
HMA Grading: 3/4 inch
Lot number:
Sublot number:
HMA Mix Number:
Binder content (%):
Virgin binder PG:
Design binder PG:
Binder Supplier:
RAP content (%):
WMA Additives:
Antistrip type:

Test Results

Test 1 of 6

DIME Test ID: 2025-06-03-25-1
Test Method: AASHTO T209-22: Standard Method of Test for Theoretical Maximum Specific Gravity (Gmm) and Density of Asphalt Mixtures (Maximum Specific Gravity)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
Number of Samples 1
What is the unit of measurement for theoretical density? US Units
Mass Determination Air
Method Performed Mechanical Agitation - Method A
Mass of container filled with water 1 7310.5 grams
Mass of oven-dry sample in air for Sample 1 2091 grams
Mass of container filled with the sample and water for Sample 1 8554.5 grams
Temperature of Water 77.2 °F
Specific Gravity for Sample 1 2.469
Theoretical maximum density at 25°C (77°F) 153.7 lb/ft^3

Test 2 of 6

DIME Test ID: 2025-06-03-25-2
Test Method: AASHTO T308-10: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
What temperature unit is used? Celsius
Test procedure used? Method A
Mass of the specimen basket assembly 4274 g
Mass of the specimen and specimen basket assembly prior to ignition 6362.6 g
Mass of HMA Sample prior to ignition 2088.6 g
Corrected Asphalt Binder Content 4.56 %
Mass Loss 107.4 g
Mass of aggregate remaining after ignition 1981.2 g
Correction Factor (Percent by mass of HMA Specimen) 0.58 %
Moisture Content no data0 %
Temperature Compensation Factor no data0 %
Test Temperature 538 C

Test 3 of 6

DIME Test ID: 2025-06-03-25-3
Test Method: AASHTO T275-07r12: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Paraffin-Coated Specimens (Bulk Specific Gravity)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
Bulk Specific Gravity 2.371
Bulk Specific Gravity 2 2.378
Bulk Specific Gravity 3 2.373
Average Bulk Specific Gravity 2.374

Test 4 of 6

DIME Test ID: 2025-06-03-25-4
Test Method: AASHTO T269-14: Standard Method of Test for Percent Air Voids in Compacted Dense and Open Asphalt Mixtures (Air Void)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
Percent Air Voids 4 %
Percent Air Voids 2 3.7 %
Percent Air Voids 3 3.9 %
Average Percent Air Voids 3.9 %

Test 5 of 6

DIME Test ID: 2025-06-03-25-5
Test Method: AASHTO T166-16: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Saturated Surface-Dry Specimens (Method A)
Verified Date: 06/05/2025
Date Tested: 06/03/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-1
Test Result Compliance: complies
Additional Comments When Verified:
Number of tests 6
Bulk Specific Gravity 1 2.279
Bulk Specific Gravity 2 2.308
Bulk Specific Gravity 3 2.319
Bulk Specific Gravity 4 2.306
Bulk Specific Gravity 5 2.308
Bulk Specific Gravity 6 2.308
Percent of water absorbed by volume 1 0.47 %
Percent of water absorbed by volume 2 0.35 %
Percent of water absorbed by volume 3 0.43 %
Percent of water absorbed by volume 4 0.36 %
Percent of water absorbed by volume 5 0.42 %
Percent of water absorbed by volume 6 0.25 %
Average Bulk Specific Gravity 2.305

Test 6 of 6

DIME Test ID: 2025-06-03-25-6
Test Method: AASHTO T324-14: Standard Method of Test for Hamburg Wheel-Track Testing of Compacted Asphalt Mixtures (Hamburg Wheel Track)
Verified Date: 06/05/2025
Date Tested: 06/05/2025
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: JMF-01
Test Result Compliance: complies
Additional Comments When Verified:
Specified minimum number of passes at ½” rut depth, or number of passes at ½” rut depth if applicable (Wheel A) 15000
Specified minimum number of passes at ½” rut depth, or number of passes at ½” rut depth if applicable (Wheel B) 15000
Impression at specified number of passes, or specified maximum impression if applicable (Wheel A) 3.09 mm
Impression at specified number of passes, or specified maximum impression if applicable (Wheel B) 2.24 mm
Stripping Inflection Point (Wheel A) 0
Stripping Inflection Point (Wheel B) 0