Sample Record for 2025-05-28-46

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1001283 DEA: 010Q0304 EFIS: 0125000108 QA Service Level: 1
DIST-CO-RTE-PM: 01-HUM-36-27.0/27.9
Work Description: Repair Storm Damage
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Joaquin Rodriguez Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2025-05-28-46
TL Number from the TL Form: 00000
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Verification
Type of Material: Asphalt Binder
Sample Taken Date: 05/28/2025
Date that the sample was received by the laboratory/organization performing the testing: 06/02/2025
The quantity of what the sample constitutes: 1 can
A brief description of the sample: PG 58-22, FEEDLINE
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Mercer Fraser Dinsmore

Material Information

Performance Grade: PG 58-22
Modified: No
Lot number:
Sublot number:
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Valero Marketing & Supply - Benicia CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:

Test Results

Test 1 of 9

DIME Test ID: 2025-05-28-46-1
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (530) 713-6823
Data has not been verified.

Test 2 of 9

DIME Test ID: 2025-05-28-46-2
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Submitted By Organization: Atlas - Denver
Organization Address: 627 Sheridan Boulevard,
Organization City: Lakewood
Organization State: CO
Organization Zipcode: 80214
Organization Email:
Organization Phone: 303-975-9959
This test has been superseded on 06/25/2025. The corrected test ID is: 2025-05-28-46-10
Reason: retested

Test 3 of 9

DIME Test ID: 2025-05-28-46-3
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/25/2025
Date Tested: 06/11/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase RTFO residue
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 10.05 %
Stress Amplitude 0.607 kPa
Phase Angle (δ) (for the 10 cycles) 79.1 degree
Complex Modulus (G*) (for the 10 measurements) 6.044 kPa
Test Temperature (Specimen 1) 58.0 C
Dynamic Shear, G*/sin(δ) 6.16 kPa

Test 4 of 9

DIME Test ID: 2025-05-28-46-4
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/25/2025
Date Tested: 06/12/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase PAV residue
Test Plate Diameter 8 mm
Test Gap 2 mm
Test Frequency 10.0 rad/s
Strain Amplitude 1.01 %
Stress Amplitude 53.047 kPa
Phase Angle (δ) (for the 10 cycles) 47.1 degree
Complex Modulus (G*) (for the 10 measurements) 5278.069 kPa
Test Temperature (Specimen 1) 22.0 C
(G*) x sin(δ)= 3866 kPa

Test 5 of 9

DIME Test ID: 2025-05-28-46-5
Test Method: AASHTO T313-22: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 06/25/2025
Date Tested: 06/11/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: BBR
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s -12.1 C
Maximum test bath temperature at 240 s -12 C
Time of test load application no data HH:MM:SS
File name of test data no data
Time beam in bath no data
Time test started no data HH:MM:SS
Flags issued by software during test no data
Correlation coefficient (R²) no data0
Regression coefficient a no data
Regression coefficient b no data
Regression coefficient c no data
Load at time 0.0 no data0 mN
Deflection at time 0.0 s no data0 µm
Load at time 0.5 s no data0 mN
Deflection at time 0.5 s no data0 µm
Load at 60.0 s no data0 mN
Beam deflection 60.0 s no data0 µm
Measured Stiffness Modulus 60.0 s no data
Estimated Stiffness Modulus 60.0 s 151.5 MPa
Difference between stiffness moduli 60.0 s no data
Estimated m-value 60.0 s 0.342

Test 6 of 9

DIME Test ID: 2025-05-28-46-6
Test Method: AASHTO T316-22: Standard Method of Test for Viscosity Determination of Asphalt Binder Using Rotational Viscometer
Verified Date: 06/25/2025
Date Tested: 06/13/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: Viscosity @ 135c
Test Result Compliance: complies
Additional Comments When Verified:
Is viscosity reading in cP/Pa-s? cP
Time of test 00:00 HH:MM
Test Temperature 134.9 C
Speed 20 rpm
Spindle size .463 in
Torque 13.2 %
Viscosity reading #1 (A) 330 cP
Viscosity reading #2 (B) 330.1 cP
Viscosity reading #3 (C) 330 cP
Average viscosity 0.33 Pa-s

Test 7 of 9

DIME Test ID: 2025-05-28-46-7
Test Method: AASHTO T240-23: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 06/25/2025
Date Tested: 06/13/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: Mass Change
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers? Two
Is mass change correction factor needed? Yes
Any material loss from containers during heating process/testing? No
Mass of container #1 before test (m1i) 203.105 grams
Mass of container #2 before test (m2i) 210.154 grams
Mass of container #1 after test (m1f) 202.938 grams
Mass of container #2 after test (m2f) 209.99 grams
Average mass change -0.445 percent
Mass of empty container #1 168.091 grams
Mass of empty container #2 175.445 grams
Mass correction factor 0.03

Test 8 of 9

DIME Test ID: 2025-05-28-46-9
Test Method: AASHTO T51-22: Standard Method of Test for Ductility of Asphalt Materials (Asphalt Binder)
Verified Date: 06/25/2025
Date Tested: 06/25/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: Ductility
Test Result Compliance: complies
Additional Comments When Verified:
Is a normal test obtainable? Yes
Number of replicates tested Three
Ductility of test #1 (D1) 150 cm
Ductility of test #2 (D2) 150 cm
Ductility of test #3 (D3) 150 cm
Ductility of sample 150 cm

Test 9 of 9

DIME Test ID: 2025-05-28-46-10
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/25/2025
Date Tested: 06/25/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: Original
The test was superseded from test ID: 2025-05-28-46-2
Test Result Compliance: does not comply
Additional Comments When Verified:
Phase Original binder
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 12.00 %
Stress Amplitude 0.260 kPa
Phase Angle (δ) (for the 10 cycles) 84.3 degree
Complex Modulus (G*) (for the 10 measurements) 2.153 kPa
Test Temperature (Specimen 1) 58.0 C
Dynamic Shear, G*/sin(δ) 2.16 kPa