Sample Record for 2025-05-08-65

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000698 DEA: 024H0704 EFIS: 0218000074 QA Service Level: 1
DIST-CO-RTE-PM: 02-LAS-139-0.74/11.0
Work Description: PLACE HMA (TYPE A), TRAFFIC CONTROL SYSTEM, TRAFFIC STRIPE, RDWY EXC.
Location Description: LASSEN COUNTY NEAR SUSANVILLE FROM 0.1 MILE NORTH OF CHESTNUT STREET TO 2.6 MILES SOUTH OF HORSE LAKE ROAD
Contractor Name: HAT CREEK CONSTRUCTION & MATERIALS, INC.
Contractor Address: Unknown
Resident Engineer: Daniel Gibbs Structure Rep.: Tooraj Yegan

Sample Information

DIME Sample ID: 2025-05-08-65
TL Number from the TL Form: 859027
Sample Submitted By Organization: Atlas - Denver
Sample Organization Contact: 303-975-9959
Type of Sample: Quality Assurance
Type of Material: Asphalt Binder
Sample Taken Date: 05/08/2025
Date that the sample was received by the laboratory/organization performing the testing: 05/19/2025
The quantity of what the sample constitutes: 2 Cans
A brief description of the sample: PG 58-34
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Hot Creek Word Lake

Material Information

Performance Grade: PG 58-34
Modified: No
Lot number:
Sublot number:
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Albina Asphalt (Klamath Falls Plant) - Klamath Falls OR
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:

Test Results

Test 1 of 8

DIME Test ID: 2025-05-08-65-1
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/06/2025
Date Tested: 06/02/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: Original
Test Result Compliance: complies
Additional Comments When Verified:
Phase Original binder
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 12.06 %
Stress Amplitude 0.130 kPa
Phase Angle (δ) (for the 10 cycles) 82.6 degree
Complex Modulus (G*) (for the 10 measurements) 1.078 kPa
Test Temperature (Specimen 1) 58.0 C
Dynamic Shear, G*/sin(δ) 1.09 kPa

Test 2 of 8

DIME Test ID: 2025-05-08-65-2
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/06/2025
Date Tested: 06/03/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase RTFO residue
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 10.05 %
Stress Amplitude 0.271 kPa
Phase Angle (δ) (for the 10 cycles) 76.7 degree
Complex Modulus (G*) (for the 10 measurements) 2.701 kPa
Test Temperature (Specimen 1) 58.0 C
Dynamic Shear, G*/sin(δ) 2.78 kPa

Test 3 of 8

DIME Test ID: 2025-05-08-65-3
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/06/2025
Date Tested: 06/04/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase PAV residue
Test Plate Diameter 8 mm
Test Gap 2 mm
Test Frequency 10.0 rad/s
Strain Amplitude 1.01 %
Stress Amplitude 44.749 kPa
Phase Angle (δ) (for the 10 cycles) 44.1 degree
Complex Modulus (G*) (for the 10 measurements) 4452.394 kPa
Test Temperature (Specimen 1) 16.0 C
(G*) x sin(δ)= 3098 kPa

Test 4 of 8

DIME Test ID: 2025-05-08-65-4
Test Method: AASHTO T313-22: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 06/06/2025
Date Tested: 06/04/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: BBR
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s -24 C
Maximum test bath temperature at 240 s -24 C
Time of test load application no data HH:MM:SS
File name of test data no data
Time beam in bath no data
Time test started no data HH:MM:SS
Flags issued by software during test no data
Correlation coefficient (R²) no data0
Regression coefficient a no data
Regression coefficient b no data
Regression coefficient c no data
Load at time 0.0 no data0 mN
Deflection at time 0.0 s no data0 µm
Load at time 0.5 s no data0 mN
Deflection at time 0.5 s no data0 µm
Load at 60.0 s no data0 mN
Beam deflection 60.0 s no data0 µm
Measured Stiffness Modulus 60.0 s no data
Estimated Stiffness Modulus 60.0 s 215 MPa
Difference between stiffness moduli 60.0 s no data
Estimated m-value 60.0 s 0.308

Test 5 of 8

DIME Test ID: 2025-05-08-65-5
Test Method: AASHTO T51-22: Standard Method of Test for Ductility of Asphalt Materials (Asphalt Binder)
Verified Date: 06/06/2025
Date Tested: 06/04/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: Ductility
Test Result Compliance: complies
Additional Comments When Verified:
Is a normal test obtainable? Yes
Number of replicates tested Three
Ductility of test #1 (D1) 150 cm
Ductility of test #2 (D2) 150 cm
Ductility of test #3 (D3) 150 cm
Ductility of sample 150 cm

Test 6 of 8

DIME Test ID: 2025-05-08-65-6
Test Method: AASHTO T316-22: Standard Method of Test for Viscosity Determination of Asphalt Binder Using Rotational Viscometer
Verified Date: 06/06/2025
Date Tested: 06/04/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: Viscosity @135C
Test Result Compliance: complies
Additional Comments When Verified:
Is viscosity reading in cP/Pa-s? cP
Time of test 09:00 HH:MM
Test Temperature 135 C
Speed 20 rpm
Spindle size .463 in
Torque 11.8 %
Viscosity reading #1 (A) 295 cP
Viscosity reading #2 (B) 294.8 cP
Viscosity reading #3 (C) 295.1 cP
Average viscosity 0.295 Pa-s

Test 7 of 8

DIME Test ID: 2025-05-08-65-8
Test Method: AASHTO T240-23: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 06/06/2025
Date Tested: 06/03/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: Mass Change
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers? Two
Is mass change correction factor needed? Yes
Any material loss from containers during heating process/testing? No
Mass of container #1 before test (m1i) 212.587 grams
Mass of container #2 before test (m2i) 208.978 grams
Mass of container #1 after test (m1f) 212.373 grams
Mass of container #2 after test (m2f) 208.779 grams
Average mass change -0.563 percent
Mass of empty container #1 177.731 grams
Mass of empty container #2 174.202 grams
Mass correction factor 0.03

Test 8 of 8

DIME Test ID: 2025-05-08-65-9
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 06/06/2025
Date Tested: 05/20/2025
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (530) 713-6823
General Comments for this Test: Original
Test Result Compliance:
Additional Comments When Verified:
Phase Original binder
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 12.00 %
Stress Amplitude 0.131 kPa
Phase Angle (δ) (for the 10 cycles) 82.6 degree
Complex Modulus (G*) (for the 10 measurements) 1.086 kPa
Test Temperature (Specimen 1) 58.0 C
Dynamic Shear, G*/sin(δ) 1.10 kPa