Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 215620 DEA: 01436404 EFIS: 0100000193
QA Service Level: 1
DIST-CO-RTE-PM: 01-DN-101-35.8/36.5
Work Description: Dr. Fine Bridge Replacement
Location Description: DR. FINE BRIDGE REPLACEMENT FROM LAKE EARL DR TO S FRED D. HAIGHT DR ON HWY 101 ACROSS SMITH RIVER.
Contractor Name: MCM Construction
Contractor Address: PO Box 620, North Highlands, Ca 95660
Resident Engineer: Clayton Malmberg Structure Rep.: Brian Cinkutis
DIME Sample ID: 2025-05-19-5
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Welded Hoops
Sample Taken Date: 05/19/2025
Date that the sample was received by the laboratory/organization performing the testing: 05/21/2025
The quantity of what the sample constitutes: 75
A brief description of the sample: #8 X4'-6"
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: TNT Rebar
Production or Authorization Testing: Production Testing
Service or Ultimate: Ultimate
Rebar Heat Number(s): 9005497
Hoop Manufacturer Lot Number(s): Lot 1
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Size: #8
Diameter of Hoop: 4'-6"
Epoxy Coated: No
Epoxy Coating Color: NA
Rebar Manufacturer: CMC Rebar
Welding Company: TNT Rebar Company
Coating Standards: Uncoated
Weld Type: Flash Welded
DIME Test ID: 2025-05-19-5-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 06/03/2025
Date Tested: 06/03/2025
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
4
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 1 | 8 | 0.79 | 73450 | 92975 | ok necking | Atlas | | 2 | 1 | 8 | 0.79 | 73650 | 93228 | ok necking | Atlas | | 3 | 1 | 8 | 0.79 | 72390 | 91633 | ok necking | Atlas | | 4 | 1 | 8 | 0.79 | 73150 | 92595 | ok necking | Atlas |
| |
|
UTM
|
NA
|
|
Temperature
|
0 f
|