Project Information

Project ID: 1000409 DEA: 051S1604 EFIS: 0524000176 QA Service Level: 1
DIST-CO-RTE-PM: 05-MON-1-60
Work Description: Rocky Creek Slip Out Permanent Restoration Project
Location Description:
Contractor Name: Gordon N Ball, Inc. (Fred Velasco/Stuart Yamamoto)
Contractor Address: 333 Camille Avenue, Alamo, CA 94507
Resident Engineer: Jorge Uberhuaga Structure Rep.: Daniel Dait

Sample Information

DIME Sample ID: 2025-05-09-13
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Sacramento Field Office
Sample Organization Contact: (916) 2058871
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 05/09/2025
Date that the sample was received by the laboratory/organization performing the testing: 05/15/2025
The quantity of what the sample constitutes: 4
A brief description of the sample: 4 samples (1 lot) of #6 rebar with EL20SAES Form Savers
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Camblin Steel

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Nucor
Coupler Manufacturer: nVent Lenton
Intermediate Assembler or Fabricator:
Rebar Size: #6
Coupler Model: nVent Lenton Form Saver
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): M0222
Rebar Heat Number(s): 1201059473, 1201059218
Rebar Size 2 :
Coupler Unique ID: ST-17-05

Test Results

Test 1 of 1

DIME Test ID: 2025-05-09-13-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 05/27/2025
Date Tested: 05/27/2025
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 4
SampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
1160.440.0034065092500service spliceKleinfelder
2160.4400004160094500service spliceKleinfelder
3160.4400004084093000service spliceKleinfelder
4160.4400004112093500service spliceKleinfelder
Temperature 0 f
UTM NA
Halo ID na