Print Report | Back to Sample Detail

Sample Record for 2025-03-10-72

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215741 DEA: 01366004 EFIS: 0100000127 QA Service Level: 1
DIST-CO-RTE-PM: 01-HUM-101-80.0/84.0
Work Description: Indianola Cutoff UC
Location Description: HUMBOLDT COUNTY NEAR EUREKA FROM EUREKA SLOUGH BRIDGE TO BAYSIDE CUTOFF
Contractor Name: Granite Construction Company
Contractor Address: 1324 S. State Street, Ukiah, CA 95482
Resident Engineer: Efren Banuelos Structure Rep.: Adlai Evans

Sample Information

DIME Sample ID: 2025-03-10-72
TL Number from the TL Form:
Sample Submitted By Organization: SHN Engineers & Geologists, Incorporated
Sample Organization Contact: (707) 441-8855
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 03/10/2025
Date that the sample was received by the laboratory/organization performing the testing: 03/11/2025
The quantity of what the sample constitutes: 3 CY
A brief description of the sample: PCC
From where was the sample collected: Source
Laboratory sample identification: C9797
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Eureka Ready Mix

Material Information

The concrete mix design number: E750FBR
The truck number from where the sample was collected: 98
The batch plant ticket number from where the sample was collected: 41317
Concrete batch plant: Eureka Ready Mix
The fabricator/manufacturer designation for the sample: Trial Batch
A detailed description of where the material sample was collected: Discharge from truck into wheelbarrow
Where the material sample would have been placed if not sampled: Trial Batch
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 6

DIME Test ID: 2025-03-10-72-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/08/2025
Date Tested: 03/17/2025
Submitted By Organization: SHN Engineers & Geologists, Incorporated
Organization Address: 812 West Wabash Avenue,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: dgonzales@shn-engr.com
Organization Phone: (707) 441-8855
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Compressive strength of cylinder (to nearest 10 psi) 5600 psi
Maximum load on cylinder 1 70440 lb
Type of fracture pattern of cylinder 1 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Age of specimen 7 days
Age of specimen in hours no data0 hours

Test 2 of 6

DIME Test ID: 2025-03-10-72-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 04/08/2025
Date Tested: 03/10/2025
Submitted By Organization: SHN Engineers & Geologists, Incorporated
Organization Address: 812 West Wabash Avenue,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: dgonzales@shn-engr.com
Organization Phone: (707) 441-8855
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Slump 4.5 inch

Test 3 of 6

DIME Test ID: 2025-03-10-72-3
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 04/08/2025
Date Tested: 03/10/2025
Submitted By Organization: SHN Engineers & Geologists, Incorporated
Organization Address: 812 West Wabash Avenue,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: dgonzales@shn-engr.com
Organization Phone: (707) 441-8855
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 60 F

Test 4 of 6

DIME Test ID: 2025-03-10-72-4
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 04/08/2025
Date Tested: 03/10/2025
Submitted By Organization: SHN Engineers & Geologists, Incorporated
Organization Address: 812 West Wabash Avenue,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: dgonzales@shn-engr.com
Organization Phone: (707) 441-8855
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Air content 2 %

Test 5 of 6

DIME Test ID: 2025-03-10-72-5
Test Method: ASTM C138-17a: Standard Test Method for Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
Verified Date: 04/08/2025
Date Tested: 03/10/2025
Submitted By Organization: SHN Engineers & Geologists, Incorporated
Organization Address: 812 West Wabash Avenue,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: dgonzales@shn-engr.com
Organization Phone: (707) 441-8855
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Identification of concrete represented by the sample E750FBR
Volume of the measure 0.25 ft^3
Density of concrete 148.9 lb/ft^3
Yield of concrete no data
Relative yield of the batch no data
Cement content no data
Air content 2 %

Test 6 of 6

DIME Test ID: 2025-03-10-72-6
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/08/2025
Date Tested: 04/07/2025
Submitted By Organization: SHN Engineers & Geologists, Incorporated
Organization Address: 812 West Wabash Avenue,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: dgonzales@shn-engr.com
Organization Phone: (707) 441-8855
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 5
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Average diameter of cylinder 4 4.00 in
Average diameter of cylinder 5 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Cross sectional area of cylinder 4 12.57 in^2
Cross sectional area of cylinder 5 12.57 in^2
Compressive strength (to nearest 10 psi) 6940 psi
Maximum load on cylinder 1 89100 lb
Maximum load on cylinder 2 90160 lb
Maximum load on cylinder 3 87740 lb
Maximum load on cylinder 4 86880 lb
Maximum load on cylinder 5 82240 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 5
Type of fracture pattern of cylinder 4 3
Type of fracture pattern of cylinder 5 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Correction factor for cylinder 4 1
Correction factor for cylinder 5 1
Age of specimen 28 days
Age of specimen in hours no data0 hours