Sample Record for 2025-04-02-1
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 1001009 DEA: 043X0504 EFIS: 0425000193
QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-116-10.4
Work Description: Apply traffic control systems, remove dirt and debris from slide, install RSP, drainage, erosion control, and reestablish MGS System.
Location Description: In Sonoma County on State Route 116 at PM 10.4 near Montesano.
Contractor Name: Piazza Construction (James Piazza)
Contractor Address: P.O. Box 573, Penngrove, CA 94951
Resident Engineer: Lenard Brajnikoff Structure Rep.: Nick Abuhamdieh
Sample Information
DIME Sample ID: 2025-04-02-1
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Santa Rosa
Sample Organization Contact: (510) 774-6009
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 04/02/2025
Date that the sample was received by the laboratory/organization performing the testing: 04/03/2025
The quantity of what the sample constitutes: 18 CY
A brief description of the sample: Type II Cement
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: River Ready Mix
Material Information
The concrete mix design number: 72203043F
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 001
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Concrete from wheelbarrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 2
DIME Test ID: 2025-04-02-1-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 04/10/2025
Date Tested: 04/09/2025
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Apparent mass of submerged cylinder 1
|
1 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4250 psi
|
|
Maximum load on cylinder 1
|
55370 lb
|
|
Maximum load on cylinder 2
|
51910 lb
|
|
Maximum load on cylinder 3
|
53420 lb
|
|
Compressive strength of cylinder 1
|
4400.0 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
4110.0 psi
|
|
Compressive strength of cylinder 3
|
4250 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|
Test 2 of 2
DIME Test ID: 2025-04-02-1-2
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 05/02/2025
Date Tested: 04/30/2025
Submitted By Organization: Quality Assurance Engineering, Inc dba Consolidated Engineering Laboratories
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Apparent mass of submerged cylinder 1
|
9 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
7570 psi
|
|
Maximum load on cylinder 1
|
95090 lb
|
|
Maximum load on cylinder 2
|
95750 lb
|
|
Maximum load on cylinder 3
|
94770 lb
|
|
Compressive strength of cylinder 1
|
7560.0 psi
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Compressive strength of cylinder 2
|
7620.0 psi
|
|
Compressive strength of cylinder 3
|
7540 psi
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Type of fracture pattern of cylinder 3
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
29 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|