Sample Record for 2025-02-10-35

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215401 DEA: 040Q3004 EFIS: 0418000069 COOP: 042776 QA Service Level: 2
DIST-CO-RTE-PM: 04-ALA-680-R10.6/R21.9
Work Description: I-680 Southbound express lanes and rehabilitation
Location Description: I- 680 Southbound from State Route (SR) 84 to Alcosta Boulevard in Alameda County
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2025-02-10-35
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Vallejo Field Laboratory
Sample Organization Contact: 9166394315
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 02/10/2025
Date that the sample was received by the laboratory/organization performing the testing: 03/10/2025
The quantity of what the sample constitutes: 3 cylinders
A brief description of the sample: 4x8 3 cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Collected at jobsite

Material Information

The concrete mix design number: 172761
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 172761
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: 4x8 3 cylinder
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2025-02-10-35-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 03/10/2025
Date Tested: 03/10/2025
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Apparent mass of submerged cylinder 1 1 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 3970 psi
Maximum load on cylinder 1 48520 lb
Maximum load on cylinder 2 51000 lb
Maximum load on cylinder 3 51851 lb
Compressive strength of cylinder 1 3820.0 psi
Type of fracture pattern of cylinder 1 4
Compressive strength of cylinder 2 4020.0 psi
Compressive strength of cylinder 3 4080 psi
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 0.99
Correction factor for cylinder 2 0.99
Correction factor for cylinder 3 0.99
Age of specimen 28 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data