Sample Record for 2025-03-07-1
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 993446 DEA: 120J34U4 EFIS: 1218000034
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-55,55-29.6,R6.4/10.3
Work Description: CONSTR BRIDGES, RW, SW, JPCP, HMA PVMT, DRAINAGE AND ELECT SYSTEMS.
Location Description: ORANGE COUNTY IN IRVINE, SANTA ANA, AND TUSTIN ON ROUTE 5 AT NEWPORT AVENUE UNDERCROSSING AND ON ROUTE 55 FROM 0.4 MILE NORTH OF ROUTE 55/405 SEPARATION TO 0.1 MILE SOUTH OF ROUTE 5/55 SEPARATION
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 3075 Townsgate Road, Suite 200, Westlake Village, CA 91361
Resident Engineer: Adrian Wu Structure Rep.: Yong Gyun Park
Sample Information
DIME Sample ID: 2025-03-07-1
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 03/07/2025
Date that the sample was received by the laboratory/organization performing the testing: 03/13/2025
The quantity of what the sample constitutes: 20 pcs
A brief description of the sample: Lot #1 / #8 rebar HRC 120 T-heads
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: HRC
Material Information
Production or Authorization Testing: Authorization Testing
Rebar Heat Number(s): 218924
Head Manufacturer Lot Number(s): Lot 1
Rebar Size: #8
Headed Bar Model Name: 8 rebar HRC 120 T heads
Size of Head: Full Size - 9x
Head Connection Type:
Head Shape: Square
Rebar Manufacturer: Cascade Steel
Head Manufacturer: HRC Fountain Valley
Head Fabricator: Nucor Utah
Material Standard Code: ASTM A706
Headed Bar Unique ID: 9FW-17-03
Test Results
Test 1 of 1
DIME Test ID: 2025-03-07-1-1
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 03/24/2025
Date Tested: 03/24/2025
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Number of Headed Bar Samples
|
4
|
| Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | | 1 | 0.79 | 75360 | 95390 | Ok Necking | Atlas | | 1 | 0.79 | 76320 | 96610 | Ok Necking | Atlas | | 1 | 0.79 | 76430 | 96750 | Ok Necking | Atlas | | 1 | 0.79 | 75830 | 95990 | Ok Necking | Atlas |
| |
|
Temperature
|
0 f
|
|
UTM
|
NA
|