Project ID: 1000115 DEA: 060Y7604 EFIS: 0619000024
QA Service Level: 1
DIST-CO-RTE-PM: 06-FRE-L5506,L5725-
Work Description: MODIFICATION OF ELECTRICAL SYSTEM.
Location Description: FRESNO COUNTY IN FRESNO AT THE WEST AVENUE MAINTENANCE STATION 1283 NORTH WEST AVENUE AND AT THE DISTRICT OFFICE 1352 WEST OLIVE AVENUE
Contractor Name: NENAD RADMANOVIC DBA RADMAN ELECTRIC
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2025-02-19-16
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 02/19/2025
Date that the sample was received by the laboratory/organization performing the testing: 02/19/2025
The quantity of what the sample constitutes: 3 concrete cylinders
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Construction H
The concrete mix design number: 1416245
The truck number from where the sample was collected: 76214
The batch plant ticket number from where the sample was collected: 41202389
Concrete batch plant: cemex
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of concrete truck, into wheelbarrow
Where the material sample would have been placed if not sampled: CT Yard
From Lot No.:
Bag Lot No.:
DIME Test ID: 2025-02-19-16-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 03/19/2025
Date Tested: 03/19/2025
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4950 psi
|
|
Maximum load on cylinder 1
|
59460 lb
|
|
Maximum load on cylinder 2
|
64640 lb
|
|
Maximum load on cylinder 3
|
62480 lb
|
|
Compressive strength of cylinder 1
|
4730.3 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
5142.4 psi
|
|
Compressive strength of cylinder 3
|
4970.6 psi
|
|
Type of fracture pattern of cylinder 2
|
5
|
|
Type of fracture pattern of cylinder 3
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|