Project Information

Project ID: 995488 DEA: 051C9504 EFIS: 0513000018 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-R36.0/R37.0
Work Description: COLD PLANE AC PVMT, RHMA, LIGHTING SYSTEMS, AND REPLACE BRIDGES.
Location Description: SANTA BARBARA COUNTY ABOUT 8.0 MILES WEST OF GOLETA FROM 0.6 MILE EAST OF REFUGIO ROAD UNDERCROSSING TO 0.4 MILE WEST OF REFUGIO ROAD UNDERCROSSING.
Contractor Name: M.C.M. CONSTRUCTION, INC.
Contractor Address: 6413 32nd Street, North Highlands, CA 95660
Resident Engineer: Jacob Cooper Structure Rep.: Clifford Replogle

Sample Information

DIME Sample ID: 2025-02-07-1
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 02/07/2025
Date that the sample was received by the laboratory/organization performing the testing: 03/07/2025
The quantity of what the sample constitutes: 80
A brief description of the sample: #14/43 mm HRC 555 T-Heads
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: HRC

Material Information

Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 3500036692
Head Manufacturer Lot Number(s): 1
Rebar Size: #14
Headed Bar Model Name: HRC 555 T Head
Size of Head: Full Size - 9x
Head Connection Type: Friction Weld
Head Shape: Circular
Rebar Manufacturer: NUCOR
Head Manufacturer: HRC
Head Fabricator: HRC
Material Standard Code: ASTM A706
Headed Bar Unique ID: 4FG-17-01

Test Results

Test 1 of 1

DIME Test ID: 2025-02-07-1-1
Test Method: ASTM A970-15e1: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 02/25/2025
Date Tested: 02/25/2025
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 4
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
12.2521614096000Broke at HeadKleinfelder
12.2521691096500Ok NeckingKleinfelder
12.2522170098500Broke at HeadKleinfelder
12.2522304099000Ok NeckingKleinfelder
Temperature 0 f
UTM NA