Sample Record for 2024-10-11-114

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 995524 DEA: 021H3604 EFIS: 0216000040 QA Service Level: 1
DIST-CO-RTE-PM: 02-SIS-96-76.8/78.0
Work Description: REPLACE BRIDGE.
Location Description: SISKIYOU COUNTY NEAR HORSE CREEK FROM 0.4 MILE WEST OF KLAMATH RIVER BRIDGE TO 2.0 MILES WEST OF KOHL CREEK
Contractor Name: MYERS & SONS CONSTRUCTION, LLC
Contractor Address: 45 Morrison Ave, Sacramento, CA 95838
Resident Engineer: Nicholas Riddle Structure Rep.: Mike Sears

Sample Information

DIME Sample ID: 2024-10-11-114
TL Number from the TL Form:
Sample Submitted By Organization: Myers and Sons Construction
Sample Organization Contact: (650) 864-2057
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 10/11/2024
Date that the sample was received by the laboratory/organization performing the testing: 10/12/2024
The quantity of what the sample constitutes: 64 Cy
A brief description of the sample: structural concrete
From where was the sample collected: Job Site
Laboratory sample identification: SC3808-1821
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: MSC

Material Information

The concrete mix design number: KSTR710
The truck number from where the sample was collected: First Truck
The batch plant ticket number from where the sample was collected: 3081
Concrete batch plant: Onsite
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Pour Site
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 4

DIME Test ID: 2024-10-11-114-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/05/2025
Date Tested: 02/05/2025
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Apparent mass of submerged cylinder 1 no data0 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 5180 psi
Maximum load on cylinder 1 69380 lb
Maximum load on cylinder 2 64780 lb
Maximum load on cylinder 3 61040 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data

Test 2 of 4

DIME Test ID: 2024-10-11-114-2
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/05/2025
Date Tested: 02/05/2025
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Apparent mass of submerged cylinder 1 no data0 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 5780 psi
Maximum load on cylinder 1 73750 lb
Maximum load on cylinder 2 70600 lb
Maximum load on cylinder 3 73620 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data

Test 3 of 4

DIME Test ID: 2024-10-11-114-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/05/2025
Date Tested: 12/03/2024
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Apparent mass of submerged cylinder 1 no data0 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 3150 psi
Maximum load on cylinder 1 40310 lb
Maximum load on cylinder 2 39900 lb
Maximum load on cylinder 3 38510 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 7 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data

Test 4 of 4

DIME Test ID: 2024-10-11-114-4
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/05/2025
Date Tested: 02/05/2025
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Apparent mass of submerged cylinder 1 no data0 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 5430 psi
Maximum load on cylinder 1 40310 lb
Maximum load on cylinder 2 39900 lb
Maximum load on cylinder 3 38519 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data