Print Report | Back to Sample Detail

Sample Record for 2025-01-31-5

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000829 DEA: 061H6104 EFIS: 0625000083 QA Service Level: 1
DIST-CO-RTE-PM: 06-TUL-99-22.74
Work Description:
Location Description:
Contractor Name: MCM Construction, Inc.
Contractor Address: PO Box 620, North Highlands, CA 95660
Resident Engineer: Unknown Structure Rep.: Luis Guzman

Sample Information

DIME Sample ID: 2025-01-31-5
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Verification
Type of Material: Concrete
Sample Taken Date: 01/31/2025
Date that the sample was received by the laboratory/organization performing the testing: 02/03/2025
The quantity of what the sample constitutes: 71.5 CY
A brief description of the sample: Type II Cement
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: NB 99 bridge over Tulare Creek
The fabricator/manufacturer/facility name: CALPORTLAND

Material Information

The concrete mix design number: 2804HF
The truck number from where the sample was collected: Load 2 Truck 1796
The batch plant ticket number from where the sample was collected: 223219
Concrete batch plant: Tulare Plant
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled: Pier Walls
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2025-01-31-5-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/07/2025
Date Tested: 02/07/2025
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 3740 psi
Maximum load on cylinder 1 46480 lb
Maximum load on cylinder 2 46400 lb
Maximum load on cylinder 3 47980 lb
Compressive strength of cylinder 1 3697.7 psi
Type of fracture pattern of cylinder 1 5
Compressive strength of cylinder 2 3691.3 psi
Compressive strength of cylinder 3 3817 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 7 days
Age of specimen in hours no data0 hours