Print Report | Back to Sample Detail

Sample Record for 2025-01-07-36

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 993333 DEA: 04264724 EFIS: 0419000068 QA Service Level: 1
DIST-CO-RTE-PM: 04-MRN-101-R20.8/27.1
Work Description: CIP BRIDGES, CONSTRUCT ROADWAY, RETAINING WALLS AND MODIFY ELECTRICAL.
Location Description: MARIN COUNTY IN AND NEAR NOVATO FROM 0.1 MILE SOUTH OF FRANKLIN AVENUE OVERHEAD TO 0.5 MILE SOUTH OF SAN ANTONIO CREEK BRIDGE
Contractor Name: GHILOTTI CONSTRUCTION CO. INC. (RILEY GENAZZI & JOSH SERAFINO)
Contractor Address: 246 GHILOTTI AVE., SANTA ROSA, CA 95407
Resident Engineer: Fabio La Serna Structure Rep.: Jeremy Light

Sample Information

DIME Sample ID: 2025-01-07-36
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Novato Field Office
Sample Organization Contact: (916) 621-8033
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/07/2025
Date that the sample was received by the laboratory/organization performing the testing: 01/07/2025
The quantity of what the sample constitutes: 35CY
A brief description of the sample: 3 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 27-0090L
Structure name: Franklin Bridge Barrier
The fabricator/manufacturer/facility name: Shamrock Materials Inc

Material Information

The concrete mix design number: SL4201CG
The truck number from where the sample was collected: 2429
The batch plant ticket number from where the sample was collected: 332533
Concrete batch plant: 138
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: CHUTE FROM TRUCK
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2025-01-07-36-1
Test Method: ASTM C1064-08: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 01/15/2025
Date Tested: 01/07/2025
Submitted By Organization: CT SC - 3672 - Novato Field Office
Organization Address: 384 Bel Marin Keys Boulevard, Suite 200,
Organization City: Novato
Organization State: CA
Organization Zipcode: 94949
Organization Email: josh.velono@dot.ca.gov
Organization Phone: (916) 621-8033
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Temperature 75 F

Test 2 of 3

DIME Test ID: 2025-01-07-36-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 01/15/2025
Date Tested: 01/07/2025
Submitted By Organization: CT SC - 3672 - Novato Field Office
Organization Address: 384 Bel Marin Keys Boulevard, Suite 200,
Organization City: Novato
Organization State: CA
Organization Zipcode: 94949
Organization Email: josh.velono@dot.ca.gov
Organization Phone: (916) 621-8033
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Slump 4.5 inch

Test 3 of 3

DIME Test ID: 2025-01-07-36-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/06/2025
Date Tested: 02/04/2025
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test: Cylinders did not break. Max capacity of machine = 7,000 psi.
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Apparent mass of submerged cylinder 1 9 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 6950 psi
Maximum load on cylinder 1 87990 lb
Maximum load on cylinder 2 87990 lb
Maximum load on cylinder 3 87990 lb
Compressive strength of cylinder 1 6860.0 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 7000.0 psi
Compressive strength of cylinder 3 7000 psi
Type of fracture pattern of cylinder 2 1
Type of fracture pattern of cylinder 3 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 0.98
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data