Print Report | Back to Sample Detail

Sample Record for 2024-11-15-52

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 8801 DEA: AML-CEM EFIS: AML-CEM QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for Cementitious Materials for use in Concrete Authorized Material List (AML)
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2024-11-15-52
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Annual Source Testing
Type of Material: Cementitious
Sample Taken Date: 11/15/2024
Date that the sample was received by the laboratory/organization performing the testing: 11/15/2024
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Type II/V Portland Cement
From where was the sample collected: Source
Laboratory sample identification: CM245474
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Victorville II/V Cement

Material Information

Brand: Cemex
Mill: Victorville
Type of Cementitious Material: Type II/V Cement

Test Results

Test

DIME Test ID: 2024-11-15-52-1
Test Method: ASTM C185-15a: Standard Test Method for Air Content of Hydraulic Cement Mortar
Verified Date: 03/04/2026
Date Tested: 01/30/2025
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: Tare wt. value was not provided.
Test Result Compliance:
Additional Comments When Verified:
Specific gravity 3.15
Water Content 240
The amount of flow (In percent) 86 %
The amount of water used (In percent) 68.57 %
Net Weight of Sample 850.0 grams
Air Content 6 %

Test

DIME Test ID: 2024-11-15-52-2
Test Method: ASTM C191-13: Standard Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
Verified Date: 03/04/2026
Date Tested: 02/23/2025
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Type of Water Used Type IV grade reagent water
Initial time of setting 129 min
Final time of setting 225 min

Test

DIME Test ID: 2024-11-15-52-3
Test Method: ASTM C204-11: Standard Test Methods for Fineness of Hydraulic Cement by Air-Permeability Apparatus
Verified Date: 03/04/2026
Date Tested: 03/07/2025
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Method Used Test Method A
Test Time 150 seconds
Fineness 4390 cm^2/g

Test

DIME Test ID: 2024-11-15-52-4
Test Method: ASTM C187-16: Standard Test Method for Amount of Water Required for Normal Consistency of Hydraulic Cement Paste (Water Normal Consistency)
Verified Date: 03/04/2026
Date Tested: 02/23/2025
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Mass of Water 178 g
Mass of Dry Cement 650 g
Water required for normal consistency 27.50 %

Test

DIME Test ID: 2024-11-15-52-5
Test Method: ASTM C109-21: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 03/04/2026
Date Tested: 01/24/2025
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Age of specimen 3 days
The amount of flow 108 %
The amount of water used 48.5 %
Compressive strength of 1st specimen 3580 psi
Compressive strength of 2nd specimen 3520 psi
Compressive strength of 3rd specimen 3540 psi
Average Compressive strength (to nearest 10 psi) 3550 psi

Test

DIME Test ID: 2024-11-15-52-6
Test Method: ASTM C109-21: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 03/04/2026
Date Tested: 02/28/2025
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Age of specimen 7 days
The amount of flow 108 %
The amount of water used 48.5 %
Compressive strength of 1st specimen 4680 psi
Compressive strength of 2nd specimen 4650 psi
Compressive strength of 3rd specimen 4440 psi
Average Compressive strength (to nearest 10 psi) 4590 psi

Test

DIME Test ID: 2024-11-15-52-7
Test Method: ASTM C109-21: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 03/04/2026
Date Tested: 02/18/2025
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Age of specimen 28 days
The amount of flow 108 %
The amount of water used 48.5 %
Compressive strength of 1st specimen 5600 psi
Compressive strength of 2nd specimen 5560 psi
Compressive strength of 3rd specimen 5450 psi
Average Compressive strength (to nearest 10 psi) 5540 psi

Test

DIME Test ID: 2024-11-15-52-8
Test Method: ASTM C114-23-24: Portland Cement Chemical Analysis: ASTM C114 (sections 7,16,17,18,) & ASTM C150
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
Data has not been verified.