Sample Record for 2024-12-11-24

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000634 DEA: 051R6804 EFIS: 0524000102 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-14.2
Work Description: Clear pavement, subsurface drains, construct underdrain or other pavement drainage, repair surface
Location Description:
Contractor Name: Brough Construction
Contractor Address: 634 Printz Road, Arroyo Grande, CA 93420
Resident Engineer: Luobao Cai Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2024-12-11-24
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Sample Organization Contact: (805) 621-3616
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 12/11/2024
Date that the sample was received by the laboratory/organization performing the testing: 12/11/2024
The quantity of what the sample constitutes: 8 CY
A brief description of the sample: 1 x 4 PCC Aggregates
From where was the sample collected: Supplier
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CEMEX Santa Barbara

Material Information

The concrete mix design number: 1629004
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 31446524
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2024-12-11-24-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 12/12/2024
Date Tested: 12/11/2024
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Temperature 70 F

Test 2 of 3

DIME Test ID: 2024-12-11-24-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 12/12/2024
Date Tested: 12/11/2024
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Slump 7 inch

Test 3 of 3

DIME Test ID: 2024-12-11-24-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 07/22/2025
Date Tested: 01/22/2025
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 7830 psi
Maximum load on cylinder 1 73140 lb
Maximum load on cylinder 2 112520 lb
Maximum load on cylinder 3 109550 lb
Compressive strength of cylinder 1 5818.6 psi
Type of fracture pattern of cylinder 1 5
Compressive strength of cylinder 2 8951.5 psi
Compressive strength of cylinder 3 8715.2 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days
Age of specimen in hours no data0 hours