Print Report | Back to Sample Detail

Sample Record for 2024-12-10-29

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000293 DEA: 041X3204 EFIS: 0424000308 QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-1-38.58
Work Description: Construct soldier pile wall, repair east side slide w/ concrete canvass, reconstruct roadway, reconstruct metal beam guardrail, pavement delineation, install structural shotcrete, stain concrete/shotcrete, install cable railing, and install erosions contr
Location Description: Ocean Cove (North) Emergency Wall at Walsh Landing
Contractor Name: O.C. Jones & Sons Inc. (Renan Modesto)
Contractor Address: Unknown
Resident Engineer: Harley Paulo Structure Rep.: Jim Cook

Sample Information

DIME Sample ID: 2024-12-10-29
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Santa Rosa
Sample Organization Contact: (510) 774-6009
Type of Sample: Quality Assurance
Type of Material: Concrete Core
Sample Taken Date: 12/10/2024
Date that the sample was received by the laboratory/organization performing the testing: 12/18/2024
The quantity of what the sample constitutes: 24 CY
A brief description of the sample: Core sample from test panel
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 20-0116
Structure name: Ocean Cove Emergency Wall
The fabricator/manufacturer/facility name: Canyon Rock Forestville

Material Information

Detail description: Shotcrete Wall Test Panel
Structure names: Ocean Cove Emergency Wall
Type of material: Shotcrete Mix 80201503

Test Results

Test 1 of 3

DIME Test ID: 2024-12-10-29-4
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joe.harline@dot.ca.gov
Organization Phone: (916) 206-4373
Data has not been verified.

Test 2 of 3

DIME Test ID: 2024-12-10-29-6
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 01/10/2025
Date Tested: 01/10/2025
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joe.harline@dot.ca.gov
Organization Phone: (916) 206-4373
General Comments for this Test: Testing Performed by Atlas
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 2.42 in
Average diameter of cylinder 2 2.67 in
Average diameter of cylinder 3 2.68 in
Cross sectional area of cylinder 1 4.6 in^2
Cross sectional area of cylinder 2 5.6 in^2
Cross sectional area of cylinder 3 5.64 in^2
Compressive strength (to nearest 10 psi) 5440 psi
Maximum load on cylinder 1 23850 lb
Maximum load on cylinder 2 31840 lb
Maximum load on cylinder 3 30780 lb
Compressive strength of cylinder 1 5184.8 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 5685.7 psi
Compressive strength of cylinder 3 5457.4 psi
Type of fracture pattern of cylinder 2 4
Type of fracture pattern of cylinder 3 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 23 days
Age of specimen in hours no data

Test 3 of 3

DIME Test ID: 2024-12-10-29-7
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 01/23/2025
Date Tested: 01/07/2025
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joe.harline@dot.ca.gov
Organization Phone: (916) 206-4373
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 4
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 2.42 in
Average diameter of cylinder 2 2.43 in
Average diameter of cylinder 3 2.42 in
Average diameter of cylinder 4 2.42 in
Cross sectional area of cylinder 1 4.6 in^2
Cross sectional area of cylinder 2 4.6 in^2
Cross sectional area of cylinder 3 4.6 in^2
Cross sectional area of cylinder 4 4.6 in^2
Compressive strength (to nearest 10 psi) 5990 psi
Maximum load on cylinder 1 27150 lb
Maximum load on cylinder 2 27580 lb
Maximum load on cylinder 3 27450 lb
Maximum load on cylinder 4 28230 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 3
Type of fracture pattern of cylinder 4 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Correction factor for cylinder 4 1
Age of specimen 28 days
Age of specimen in hours no data

Tests Assigned to this Sample

DIME Test IDTest MethodAssigned DateTest DateAssigned ByAssigned LabTest CommentsAssigned To
2024-12-10-29-1ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens12/18/202412/24/2024Lauren LauCT HQ - Vallejo Field Laboratory
2024-12-10-29-2ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens12/18/202401/07/2025Lauren LauCT HQ - Vallejo Field Laboratory
2024-12-10-29-3ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens12/26/202401/07/2025Spencer AdamsCT HQ - Sacramento Concrete Testing Laboratory