DIME Sample ID: 2024-12-09-9
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 12/09/2024
Date that the sample was received by the laboratory/organization performing the testing: 12/10/2024
The quantity of what the sample constitutes: 1 lot
A brief description of the sample: #11 D250L Coupler
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 42-0171
Structure name: Toulumne Street OC
The fabricator/manufacturer/facility name: Job Site
Production or Authorization Testing: Authorization Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Nucor Steel
Coupler Manufacturer: Dayton Superior
Intermediate Assembler or Fabricator:
Rebar Size: #11
Coupler Model: D250L
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): 207506 4000016126 4000016130
Rebar Heat Number(s): 3500039578
Rebar Size 2 :
Coupler Unique ID: SL-17-06
DIME Test ID: 2024-12-09-9-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 12/14/2024
Date Tested: 12/13/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Atlas Technical Consultants
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
4
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Slip (inch) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1A | 207506 | 11 | 1.56 | 0.0020 | 139760 | 89590 | Atlas Technical Consultants | Miguel Baltazar | | 2A | 207506 | 11 | 1.56 | 000 | 137150 | 87917 | Atlas Technical Consultants | Miguel Baltazar | | 3A | 207506 | 11 | 1.56 | 000 | 141250 | 90545 | Atlas Technical Consultants | Miguel Baltazar | | 4A | 207506 | 11 | 1.56 | 000 | 144330 | 92519 | Atlas Technical Consultants | Miguel Baltazar |
| |
|
Temperature
|
0 f
|
|
UTM
|
NA
|
|
Halo ID
|
000
|
DIME Test ID: 2024-12-09-9-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Necking)
Verified Date: 12/14/2024
Date Tested: 12/13/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Atlas Technical Consultants
Test Result Compliance:
Additional Comments When Verified:
|
Necking Test Option
|
Necking Test Option I
|
|
Shape of the Sample
|
Straight Sample
|
|
Sample 1 Visible Necking?
|
Yes
|
|
Sample 1 Location of Fracture?
|
Rebar
|
|
Sample 2 Visible Necking?
|
Yes
|
|
Sample 2 Location of Fracture?
|
Rebar
|
|
Sample 3 Visible Necking?
|
Yes
|
|
Sample 3 Location of Fracture?
|
Rebar
|
|
Sample 4 Visible Necking?
|
Yes
|
|
Sample 4 Location of Fracture?
|
Rebar
|