Project ID: 214135 DEA: 09213404 EFIS: 0900000030
QA Service Level: 1
DIST-CO-RTE-PM: 09-INY-395-29.9/41.8
Work Description: ROADWAY EXCAVATION, PLACE HMA (TYPE A), AND ALTERNATIVE PIPE CULVERT.
Location Description: INYO COUNTY NEAR OLANCHA AND CARTAGO FROM 1.4 MILES SOUTH OF LOS ANGELES AQUEDUCT BRIDGE TO 0.2 MILE SOUTH OF ASH CREEK BRIDGE
Contractor Name: FISHER SAND & GRAVEL CO.
Contractor Address: 1302 W DRIVERS WAY, TEPE, AZ. 85284
Resident Engineer: Kris Raber Structure Rep.: Sheila Reyes
DIME Sample ID: 2024-11-01-63
TL Number from the TL Form: 4500
Sample Submitted By Organization: CT D09 - Bishop Field Laboratory
Sample Organization Contact: (760) 872-5211
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/01/2024
Date that the sample was received by the laboratory/organization performing the testing: 11/04/2024
The quantity of what the sample constitutes: 250 cy
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: PCC-101
Structure unique identifier:
Structure name: DS 1114
The fabricator/manufacturer/facility name: 7-11 Materials Bishop
The concrete mix design number: 00-00-0000
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Middle of 1st Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2024-11-01-63-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 12/03/2024
Date Tested: 12/02/2024
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: DS 1114 NL Inlet Headwall
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4190 psi
|
|
Maximum load on cylinder 1
|
51600 lb
|
|
Maximum load on cylinder 2
|
52740 lb
|
|
Maximum load on cylinder 3
|
53590 lb
|
|
Compressive strength of cylinder 1
|
4105.0 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
4195.7 psi
|
|
Compressive strength of cylinder 3
|
4263.3 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
31 days
|
|
Age of specimen in hours
|
no data0 hours
|