Sample Record for 2024-11-12-37

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000180 DEA: 081N2604 EFIS: 0822000126 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-15-2.2/8.5
Work Description: FURNISH POLYESTER CONC OVERLAY, PLACE POLYESTER CONC OVERLAY.
Location Description: SAN BERNARDINO COUNTY IN AND NEAR FONTANA AT VARIOUS LOCATIONS FROM ROUTE 10 TO ROUTE 210
Contractor Name: MCCUEN CONSTRUCTION, INC.
Contractor Address: 3269 Swetzer Road, Loomis, CA 95650
Resident Engineer: Dominic Ehirim Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2024-11-12-37
TL Number from the TL Form: 24-147
Sample Submitted By Organization: Kwik Bond Polymers
Sample Organization Contact: (760) 518-6064
Type of Sample: Quality Control
Type of Material: Polyester
Sample Taken Date: 11/12/2024
Date that the sample was received by the laboratory/organization performing the testing: 11/13/2024
The quantity of what the sample constitutes: 2 tankers
A brief description of the sample: 1 gallon can / PPC 1121 RESIN
From where was the sample collected: Source
Laboratory sample identification: 000146KBP
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Kwik Bond Polymers, Benicia

Material Information

Mfg. Lot Number(s): AZ4K01751T
Batch number: AZ4K01751T
Mix number: AZ4K01751T

Test Results

Test 1 of 6

DIME Test ID: 2024-11-12-37-1
Test Method: ASTM D638-Dec14: Standard Test Method for Tensile Properties of Plastics
Verified Date: 12/31/2024
Date Tested: 11/19/2024
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joe.harline@dot.ca.gov
Organization Phone: (916) 206-4373
General Comments for this Test: Accepted Vendor's Results
Test Result Compliance: complies
Additional Comments When Verified:
Number of specimens tested 6
Conditioning procedure 18/25/50+5/70
Speed of testing 0.45 in/min
Sample 1 Width 0.485 in
Sample 1 Ultimate strength 2984 psi
Sample 1 Thickness 0.258 in
Sample 1 Area 0.1251 in^2
Sample 1 Ultimate Strength Actual 373.298 lbs
Sample 1 percent elongation 67.9 %
Sample 1 Time no data0 MM:SS
Sample 2 Width 0.485 in
Sample 2 Thickness 0.262 in
Sample 2 Area 0.1271 in^2
Sample 2 Ultimate strength 3224 psi
Sample 2 Ultimate Strength Actual 409.77 lbs
Sample 2 percent elongation 75.8 %
Sample 2 Time no data0 MM:SS
Sample 3 Width 0.484 in
Sample 3 Thickness 0.261 in
Sample 3 Area 0.1263 in^2
Sample 3 Ultimate strength 3225 psi
Sample 3 Ultimate Strength Actual 407.318 lbs
Sample 3 percent elongation 75.6 %
Sample 3 Time no data0 MM:SS
Sample 4 Width 0.485 in
Sample 4 Thickness 0.26 in
Sample 4 Area 0.1261 in^2
Sample 4 Ultimate strength 3163 psi
Sample 4 Ultimate Strength Actual 398.854 lbs
Sample 4 percent elongation 74.1 %
Sample 4 Time no data0 MM:SS
Sample 5 Width 0.485 in
Sample 5 Thickness 0.254 in
Sample 5 Area 0.1232 in^2
Sample 5 Ultimate strength 2997 psi
Sample 5 Ultimate Strength Actual 369.23 lbs
Sample 5 percent elongation 68.1 %
Sample 5 Time no data0 MM:SS
Sample 6 Width 0.484 in
Sample 6 Thickness 0.255 in
Sample 6 Area 0.1234 in^2
Sample 6 Ultimate strength 3266 psi
Sample 6 Ultimate Strength Actual 403.024 lbs
Sample 6 percent elongation 77.1 %
Sample 6 Time no data0 MM:SS
Ultimate Strength Average 3143 psi
Percent Elongation Average 73 %

Test 2 of 6

DIME Test ID: 2024-11-12-37-2
Test Method: CTM 551-August 2012: Method of Test for Determining Suitability of Materials for Overlayment and Repair of Portland Cement Concrete Pavements and Structures
Verified Date: 12/31/2024
Date Tested: 11/21/2024
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joe.harline@dot.ca.gov
Organization Phone: (916) 206-4373
General Comments for this Test: Accepted Vendor's Results
Test Result Compliance: complies
Additional Comments When Verified:
Curing history for Sample 1 24hr
Maximum applied load (P) for Sample 1 1332.46 lb
Span length for Sample 1 9 in
Break location for Sample 1 bond
Specimen defects/notes for Sample 1 no data
Surface type for Sample 1 SSD
Modulus of rupture (R) for Sample 1 666.232 psi
Curing history for Sample 2 24hr
Maximum applied load (P) for Sample 2 1164.75 lb
Span length for Sample 2 9 in
Break location for Sample 2 bond
Specimen defects/notes for Sample 2 no data
Surface type for Sample 2 SSD
Modulus of rupture (R) for Sample 2 582.377 psi
Curing history for Sample 3 24hr
Maximum applied load (P) for Sample 3 1585.46 lb
Span length for Sample 3 9 in
Break location for Sample 3 bond
Specimen defects/notes for Sample 3 no data
Surface type for Sample 3 SSD
Modulus of rupture (R) for Sample 3 792.729 psi

Test 3 of 6

DIME Test ID: 2024-11-12-37-3
Test Method: SCAQMD 309-91-Feb93: Determination of Static Volatile Emissions
Verified Date: 12/31/2024
Date Tested: 11/20/2024
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joe.harline@dot.ca.gov
Organization Phone: (916) 206-4373
General Comments for this Test: Accepted Vendor's Results
Test Result Compliance: complies
Additional Comments When Verified:
Diameter of lid 153.9 mm
Room Temperature 76 f
Tare weight no data
Initial weight 100.013 grams
Weight at 5 minutes 99.909 grams
Weight at 10 minutes 99.798 grams
Weight at 15 minutes 99.7 grams
Weight at 20 minutes 99.605 grams
Weight at 25 minutes 99.512 grams
Weight at 30 minutes 99.426 grams
Final weight 99.43 grams
Total weight loss 0.58 grams
Calculated radius of gallon can lid in cm 7.695 cm
Lid Factor 53.757 m^2
Volatile emission 31.34 grams/m^2

Test 4 of 6

DIME Test ID: 2024-11-12-37-4
Test Method: ASTM D2196-Feb15: Standard Test Methods for Rheological Properties of Non-Newtonian Materials by Rotational Viscometer
Verified Date: 06/18/2025
Date Tested: 06/17/2025
Submitted By Organization: Future Labs, LLC
Organization Address: 124 Lone Wolf Drive,
Organization City: Madison
Organization State: MS
Organization Zipcode: 39110
Organization Email: alexh@futurelabsllc.com
Organization Phone:
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Viscosity 84.5

Test 5 of 6

DIME Test ID: 2024-11-12-37-5
Test Method: ASTM D1475-Nov13: Standard Test Method For Density of Liquid Coatings, Inks, and Related Products
Verified Date: 06/18/2025
Date Tested: 06/17/2025
Submitted By Organization: Future Labs, LLC
Organization Address: 124 Lone Wolf Drive,
Organization City: Madison
Organization State: MS
Organization Zipcode: 39110
Organization Email: alexh@futurelabsllc.com
Organization Phone:
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Density Units pounds/gallons
Liquid Density (pounds per gallon) 9

Test 6 of 6

DIME Test ID: 2024-11-12-37-6
Test Method: ASTM D2369-Jul10: Standard Test Method for Volatile Content of Coatings
Verified Date: 06/18/2025
Date Tested: 06/17/2025
Submitted By Organization: Future Labs, LLC
Organization Address: 124 Lone Wolf Drive,
Organization City: Madison
Organization State: MS
Organization Zipcode: 39110
Organization Email: alexh@futurelabsllc.com
Organization Phone:
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Mean of two volatile content determination 46