Project ID: 994326 DEA: 051C3604 EFIS: 0512000134
QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-217-0.9/1.4
Work Description: REPLACE BRIDGE.
Location Description: SANTA BARBARA COUNTY NEAR GOLETA FROM 0.2 MILE EAST OF GOLETA SLOUGH BRIDGE TO 0.4 MILE EAST OF SAN JOSE CREEK BRIDGE
Contractor Name: MCM CONSTRUCTION
Contractor Address: 6413 32nd Street, North Highlands, Ca 95660
Resident Engineer: Manny Yogarajah Structure Rep.: Fabian Velasco
DIME Sample ID: 2024-11-14-44
TL Number from the TL Form:
Sample Submitted By Organization: Kleinfelder, Incorporated -Sacramento
Sample Organization Contact: (916) 308-3701
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 11/14/2024
Date that the sample was received by the laboratory/organization performing the testing: 11/20/2024
The quantity of what the sample constitutes: 8 of 900
A brief description of the sample: #9 HRC 150 T-Heads
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Headed Reinforcement Corp, Fountain Valley, CA
Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 223022
Head Manufacturer Lot Number(s): 400002289021
Rebar Size: #9
Headed Bar Model Name: HRC 150 THeads
Size of Head: Full Size - 9x
Head Connection Type: Friction Weld
Head Shape: Circular
Rebar Manufacturer: Cascade Steel
Head Manufacturer: Nucor
Head Fabricator: Nucor
Material Standard Code: ASTM A706
Headed Bar Unique ID: 9FW-17-04
DIME Test ID: 2024-11-14-44-1
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 11/25/2024
Date Tested: 11/25/2024
Submitted By Organization: Kleinfelder, Incorporated -Sacramento
Organization Address: 9969 Horn Road,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95827
Organization Email: jslinkard@kleinfelder.com
Organization Phone: (916) 308-3701
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Number of Headed Bar Samples
|
4
|
| Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | | 1 | 1 | 100930 | 101000 | na | MK | | 1 | 1 | 100870 | 101000 | na | MK | | 1 | 1 | 102500 | 103000 | na | MK | | 1 | 1 | 99360 | 99500 | na | MK |
| |
|
Temperature
|
72 f
|
|
UTM
|
NA
|
DIME Test ID: 2024-11-14-44-2
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 11/25/2024
Date Tested: 11/25/2024
Submitted By Organization: Kleinfelder, Incorporated -Sacramento
Organization Address: 9969 Horn Road,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95827
Organization Email: jslinkard@kleinfelder.com
Organization Phone: (916) 308-3701
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Number of Headed Bar Samples
|
4
|
| Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | | 4 | 1 | 100220 | 100000 | na | MK | | 4 | 1 | 100250 | 100000 | na | MK | | 4 | 1 | 99570 | 99500 | na | MK | | 4 | 1 | 99150 | 99000 | na | MK |
| |
|
Temperature
|
72 f
|
|
UTM
|
NA
|