Sample Record for 2024-11-08-31
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 212470 DEA: 044A1304 EFIS: 0400001106 COOP: 042718
QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-101-18.5/18.5
Work Description: CONSISTS OF MODIFICATION AND RECONSTRUCTION OF THE EXISTING US 101/HEARN AVENUE INTERCHANGE IN SONOMA COUNTY, INCLUDING REPLACING THE EXISTING TWO-LANE HEARN AVENUE OVERCROSSING WITH A NEW OVERCROSSING, AND MODIFYING THE SOUTHBOUND OFF-RAMP IN CITY
Location Description: IN SONOMA COUNTY.
Contractor Name: Ghilotti Construction Company, Inc. (Chase McPhaul)
Contractor Address: 246 Ghilotti Avenue, Santa Rosa, CA 95407
Resident Engineer: Seyed "Syd" Valeh Structure Rep.: Anthony "Tony" Tierra; Sardar Chalabe
Sample Information
DIME Sample ID: 2024-11-08-31
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Santa Rosa
Sample Organization Contact: (510) 774-6009
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/08/2024
Date that the sample was received by the laboratory/organization performing the testing: 11/14/2024
The quantity of what the sample constitutes: 40 CY
A brief description of the sample: Concrete for Abutment 1 Footing
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Superior Supplies
Material Information
The concrete mix design number: 590CR2
The truck number from where the sample was collected: 4
The batch plant ticket number from where the sample was collected: 307345
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Taken on a flat surface next to the Abutment 1 footing
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 2
DIME Test ID: 2024-11-08-31-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/09/2024
Date Tested: 12/06/2024
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4960 psi
|
|
Maximum load on cylinder 1
|
65186 lb
|
|
Maximum load on cylinder 2
|
59283 lb
|
|
Maximum load on cylinder 3
|
63867 lb
|
|
Compressive strength of cylinder 1
|
5185.8 psi
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Compressive strength of cylinder 2
|
4669.1 psi
|
|
Compressive strength of cylinder 3
|
5030.1 psi
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Type of fracture pattern of cylinder 3
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
0.99
|
|
Correction factor for cylinder 3
|
0.99
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data
|
Test 2 of 2
DIME Test ID: 2024-11-08-31-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Submitted By Organization: CT SC - 3672 - Santa Rosa
Organization Address: 4030 Occidental, Building B,
Organization City: Santa Rosa
Organization State: CA
Organization Zipcode: 95401
Organization Email: james.cook@dot.ca.gov
Organization Phone: (707) 974-2571
Data has not been verified.