Print Report | Back to Sample Detail

Sample Record for 2024-10-16-14

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215348 DEA: 060U4204 EFIS: 0616000004 QA Service Level: 1
DIST-CO-RTE-PM: 06-FRE-99-R4.9/11.6
Work Description: CONSTRUCT CRCP, PLACE HMA, AND ROADWAY EXCAVATION.
Location Description: FRESNO COUNTY IN AND NEAR SELMA AND FOWLER FROM MCCALL AVENUE UNDERCROSSING TO 0.5 MILE NORTH OF MERCED STREET UNDERCROSSING
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 3075 Townsgate Rd. Suite 200, Westlake Village CA 91361
Resident Engineer: Chris Wilfong Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2024-10-16-14
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 10/16/2024
Date that the sample was received by the laboratory/organization performing the testing: 10/17/2024
The quantity of what the sample constitutes: 5
A brief description of the sample: 4X8 Concrete Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: Mix NCT09064
Structure unique identifier:
Structure name: CIDH Sign foundation
The fabricator/manufacturer/facility name: Builder Concrete at Sanger Plant

Material Information

The concrete mix design number: NCT09064
The truck number from where the sample was collected: Load 2
The batch plant ticket number from where the sample was collected: 111351707
Concrete batch plant: Concrete Builder at Sanger plant
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Shoulder of SB 99, STA 207+50
Where the material sample would have been placed if not sampled: Pedestal Sign foundation at Shoulder of SB 99, STA 207+50
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2024-10-16-14-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/24/2024
Date Tested: 10/24/2024
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: does not comply
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 3090 psi
Maximum load on cylinder 1 38930 lb
Maximum load on cylinder 2 39510 lb
Maximum load on cylinder 3 38170 lb
Compressive strength of cylinder 1 3097.1 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 3143.2 psi
Compressive strength of cylinder 3 3036.6 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 8 days
Age of specimen in hours no data0 hours

Test 2 of 2

DIME Test ID: 2024-10-16-14-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/13/2024
Date Tested: 11/13/2024
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test: Required strenght 4000 psi @ 28 days
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 4310 psi
Maximum load on cylinder 1 54620 lb
Maximum load on cylinder 2 53830 lb
Maximum load on cylinder 3 54080 lb
Compressive strength of cylinder 1 4345.3 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4282.4 psi
Compressive strength of cylinder 3 4302.3 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours

Tests Assigned to this Sample

DIME Test IDTest MethodAssigned DateTest DateAssigned ByAssigned LabTest CommentsAssigned To
2024-10-16-14-1CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders10/17/2024Not scheduledSok ThunCT D06 - Millbrook Field Laboratoryrequired strength 4000 @28 day