Project Information

Project ID: 994503 DEA: 042W0704 EFIS: 0421000133 MINOR: 04A6556 QA Service Level: 1
DIST-CO-RTE-PM: 04-MRN-101-
Work Description:
Location Description:
Contractor Name: CONSTRUCTION H INC
Contractor Address: 2766 Carlton Court, San Pablo, CA 94806
Resident Engineer: Dawit Habteselassie Structure Rep.: Phil Latasa

Sample Information

DIME Sample ID: 2024-09-28-12
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Novato Field Office
Sample Organization Contact: (916) 621-8033
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/28/2024
Date that the sample was received by the laboratory/organization performing the testing: 09/28/2024
The quantity of what the sample constitutes: 20CY
A brief description of the sample: 3 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: Overhead Sign Pile
The fabricator/manufacturer/facility name: Shamrock Materials Inc

Material Information

The concrete mix design number: D67112E1
The truck number from where the sample was collected: 2422
The batch plant ticket number from where the sample was collected: 303926
Concrete batch plant: 73
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: CHUTE FROM TRUCK
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test

DIME Test ID: 2024-09-28-12-1
Test Method: ASTM C1064-08: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Submitted By Organization: CT SC - 3672 - Novato Field Office
Organization Address: 384 Bel Marin Keys Boulevard, Suite 200,
Organization City: Novato
Organization State: CA
Organization Zipcode: 94949
Organization Email: josh.velono@dot.ca.gov
Organization Phone: (916) 621-8033
Data has not been verified.

Test

DIME Test ID: 2024-09-28-12-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 10/02/2024
Date Tested: 09/28/2024
Submitted By Organization: CT SC - 3672 - Novato Field Office
Organization Address: 384 Bel Marin Keys Boulevard, Suite 200,
Organization City: Novato
Organization State: CA
Organization Zipcode: 94949
Organization Email: josh.velono@dot.ca.gov
Organization Phone: (916) 621-8033
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Slump 4 inch

Test

DIME Test ID: 2024-09-28-12-4
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/07/2024
Date Tested: 11/06/2024
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Apparent mass of submerged cylinder 1 1 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 6900 psi
Maximum load on cylinder 1 84093 lb
Maximum load on cylinder 2 87990 lb
Maximum load on cylinder 3 87990 lb
Compressive strength of cylinder 1 6690.0 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 7000.0 psi
Compressive strength of cylinder 3 7000 psi
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) Strength of sample 2 & 3 is > 7000 psi. Machine capacity is 7000 psi.
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 40 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data