Project ID: 995450 DEA: 09368004 EFIS: 0917000011
QA Service Level: 1
DIST-CO-RTE-PM: 09-MNO-395-91.6/93.4
Work Description: HOT MIX ASPHALT (TYPE A), RAIL ELEMENT WALL, AND ROADWAY EXCAVATION.
Location Description: MONO COUNTY ABOUT 16 MILES NORTH OF BRIDGEPORT FROM BURCHAM FLAT ROAD TO 0.3 MILE SOUTH OF ROUTE 108
Contractor Name: PAPICH CONSTRUCTION COMPANY, INC.
Contractor Address: Unknown
Resident Engineer: raj bharathan Structure Rep.: Unknown
DIME Sample ID: 2024-09-28-1
TL Number from the TL Form:
Sample Submitted By Organization: CT D09 - Bishop Field Laboratory
Sample Organization Contact: (760) 872-5211
Type of Sample: Acceptance
Type of Material: Hot Mix Asphalt
Sample Taken Date: 09/28/2024
Date that the sample was received by the laboratory/organization performing the testing: 09/28/2024
The quantity of what the sample constitutes: 4 Boxes of HMA 0 - 750 Tons
A brief description of the sample: 3/4" HMA
From where was the sample collected: Job Site
Laboratory sample identification: HMA 24
Structure unique identifier:
Structure name: Hwy 395 / Sonora Junction
The fabricator/manufacturer/facility name: Granite Lee Vining
DIME Test ID: 2024-09-28-1-1
Test Method: AASHTO T209-22: Standard Method of Test for Theoretical Maximum Specific Gravity (Gmm) and Density of Asphalt Mixtures (Maximum Specific Gravity)
Verified Date: 09/30/2024
Date Tested: 09/30/2024
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: HMA-24
Test Result Compliance: complies
Additional Comments When Verified:
|
Number of Samples
|
1
|
|
What is the unit of measurement for theoretical density?
|
US Units
|
|
Mass Determination
|
Air
|
|
Method Performed
|
Mechanical Agitation - Method A
|
|
Mass of container filled with water 1
|
7310.5 grams
|
|
Mass of oven-dry sample in air for Sample 1
|
2175.5 grams
|
|
Mass of container filled with the sample and water for Sample 1
|
8600.3 grams
|
|
Temperature of Water
|
77.1 °F
|
|
Specific Gravity for Sample 1
|
2.456
|
|
Theoretical maximum density at 25°C (77°F)
|
152.9 lb/ft^3
|
DIME Test ID: 2024-09-28-1-2
Test Method: AASHTO T308-10: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 09/30/2024
Date Tested: 09/30/2024
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: HMA-24
Test Result Compliance: complies
Additional Comments When Verified:
|
What temperature unit is used?
|
Celsius
|
|
Test procedure used?
|
Method A
|
|
Mass of the specimen basket assembly
|
4273.6 g
|
|
Mass of the specimen and specimen basket assembly prior to ignition
|
6411.2 g
|
|
Mass of HMA Sample prior to ignition
|
2137.6 g
|
|
Corrected Asphalt Binder Content
|
5.08 %
|
|
Mass Loss
|
119.9 g
|
|
Mass of aggregate remaining after ignition
|
2017.7 g
|
|
Correction Factor (Percent by mass of HMA Specimen)
|
0.53 %
|
|
Moisture Content
|
no data0 %
|
|
Temperature Compensation Factor
|
no data0 %
|
|
Test Temperature
|
538 C
|