Gavin Newsom, Governor |
DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 041X3204 Cty SON Rte 1 PM 38.58 Vendor # |
|
REPORT OF LABORATORY TESTING |
||||
|
Resident Engineer: |
Harley Paulo |
Date Reported: |
10/16/2024 |
|
|
Address: |
TL Number: |
|
||
|
City: |
||||
|
Project Name: Construct soldier pile wall, repair east side slide w/ concrete canvass, reconstruct roadway, reconstruct metal beam guardrail, pavement delineation, install structural shotcrete, stain concrete/shotcrete, install cable railing, and install erosions contr |
||||
|
Prime Contractor: O.C. Jones & Sons Inc. (Renan Modesto) |
||||
|
Sample Taken Date: |
09/23/2024 |
Mix Design: |
72105003R |
|
|
Contractor: Unknown |
Location : Ocean Cove (North) Emergency Wall at Walsh Landing |
|||
|
Structure unique identifier: 20-0116 |
||||
|
Structure name: Ocean Cove Emergency Wall |
||||
|
Location of Pour: Concrete Waler |
||||
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
| Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
|---|---|---|---|---|---|
| 1 | 4.01 | 12.63 | 50261 | 3980.0 | 1 |
| 2 | 4.00 | 12.57 | 54225 | 4315.0 | 1 |
| 3 | 4.01 | 12.63 | 52671 | 4171 | 1 |
DIME Test ID: 2024-09-23-3-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 4160
Age of specimen: 7 days
Certified By: Spencer Adams
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
| Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
|---|---|---|---|---|---|
| 1 | 4.02 | 12.69 | 56749 | 4471.0 | 1 |
| 2 | 4.01 | 12.63 | 60027 | 4753.0 | 1 |
| 3 | 4.01 | 12.63 | 56756 | 4494 | 1 |
DIME Test ID: 2024-09-23-3-2
Number of specimens: 3
Compressive strength (to nearest 10 psi): 4570
Age of specimen: 28 days
Certified By: Spencer Adams
ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
| Temperature |
|---|
| 70 |
DIME Test ID: 2024-09-23-3-4
Certified By: Lauren Lau
ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
| Slump |
|---|
| 4 |
DIME Test ID: 2024-09-23-3-5
Certified By: Lauren Lau
Test ID: 2024-09-23-3-4: Ambient 75F
|
*Subject to final inspection by the Resident Engineer. |
|
TL- Report of Laboratory Testing